English
Language : 

DR-75 Datasheet, PDF (1/2 Pages) Total Power International – 75W Single Output Industrial DIN Rail Power Supply
TOTAL POWER INT'L
75W Single Output Industrial DIN Rail Power Supply
DR-75 series
Features :
Universal AC input/Full range
Protections:Short circuit/Over load/Over voltage/Over temperature
Cooling by free air convection
Can be installed on DIN rail TS-35/7.5 or 15
UL 508(industrial control equipment)approved
LED indicator for power on
100% full load burn-in test
Fix switching frequency at 50KHz
3 years warranty
R
SPECIFICATION
MODEL
DR-75-12
DR-75-24
DR-75-48
DC VOLTAGE
12V
24V
48V
RATED CURRENT
6.3A
3.2A
1.6A
CURRENT RANGE
0 ~ 6.3A
0 ~ 3.2A
0 ~ 1.6A
RATED POWER
76W
76.8W
76.8W
OUTPUT RIPPLE & NOISE (max.) Note.2 100mVp-p
VOLTAGE ADJ. RANGE
12 ~ 14V
150mVp-p
24 ~ 28V
240mVp-p
48 ~ 53V
VOLTAGE TOLERANCE Note.3 2.0%
1.0%
1.0%
LINE REGULATION
0.5%
0.5%
0.5%
LOAD REGULATION
1.0%
1.0%
1.0%
SETUP, RISE, HOLD TIME 1000ms, 60ms, 50ms/230VAC 1800ms, 60ms, 10ms/115VAC at full load
VOLTAGE RANGE
85 ~ 264VAC 120 ~ 370VDC
FREQUENCY RANGE
47 ~ 63Hz
EFFICIENCY (Typ.)
76%
80%
81%
INPUT
AC CURRENT
2A/115V 1.2A/230V
INRUSH CURRENT (max.) COLD START 30A/115VAC 60A/230VAC
LEAKAGE CURRENT
<1mA / 240VAC
OVER LOAD
105 ~ 150% rated output power
Protection type : Constant current limiting, recovers automatically after fault condition is removed
PROTECTION OVER VOLTAGE
15 ~ 16.5V
29 ~ 34V
58 ~ 65V
Protection type : Hiccup mode, recovers automatically after fault condition is removed
OVER TEMPERATURE
85 5 (TSW1) Detect on heat sink of power transistor
Protection type : Shut down o/p voltage, recovers automatically after temperature goes down
WORKING TEMP.
-10 ~ +60 (Refer to output load derating curve)
WORKING HUMIDITY
20 ~ 90% RH non-condensing
ENVIRONMENT STORAGE TEMP., HUMIDITY -20 ~ +85 , 10 ~ 95% RH
TEMP. COEFFICIENT
0.03%/ (0 ~ 50
VIBRATION
10 ~ 500Hz, 2G 10min./1cycle, period for 60min. each along X, Y, Z axes
SAFETY STANDARDS
UL508, TUV EN60950 Approved
SAFETY &
EMC
(Note 4)
WITHSTAND VOLTAGE
ISOLATION RESISTANCE
EMI CONDUCTION & RADIATION
HARMONIC CURRENT
I/P-O/P:3KVAC I/P-FG:1.5KVAC O/P-FG:0.5KVAC
I/P-O/P, I/P-FG, O/P-FG:100M Ohms/500VDC
Compliance to EN55011,EN55022 (CISPR22) Class B
Compliance to EN61000-3-2,-3
EMS IMMUNITY
Compliance to EN61000-4-2,3,4,5,6,8,11, ENV50204, EN55024, EN61000-6-2 (EN50082-2) Heavy industry level, criteria A
MTBF
123.1K hrs min. MIL-HDBK-217F (25 )
OTHERS DIMENSION
55.5*125.2*100mm (W*H*D)
PACKING
0.6Kg; 20pcs/13Kg/1.1CUFT
NOTE
1. All parameters NOT specially mentioned are measured at 230VAC input, rated load and 25 of ambient temperature.
2. Ripple & noise are measured at 20MHz of bandwidth by using a 12" twisted pair-wire terminated with a 0.1uf & 47uf parallel capacitor.
3. Tolerance : includes set up tolerance, line regulation and load regulation.
4. The power supply is considered a component which will be installed into a final equipment. The final equipment must be re-confirmed that it still meets
EMC directives.