7.4 Device Functional Modes
7.4.1 Power-Supply Sequencing
The UCD90120A can control the turn-on and turn-off sequencing of up to 12 voltage rails by using a GPIO to set
a power-supply enable pin high or low. In PMBus-based designs, the system PMBus master can initiate a
sequence-on event by asserting the PMBUS_CNTRL pin or by sending the OPERATION command over the I2C
serial bus. In pin-based designs, the PMBUS_CNTRL pin can also be used to sequence-on and sequence-off.
The auto-enable setting ignores the OPERATION command and the PMBUS_CNTRL pin. Sequence-on is
started at power up after any dependencies and time delays are met for each rail. A rail is considered to be on or
within regulation when the measured voltage for that rail crosses the power-good on (POWER_GOOD_ON (1))
limit. The rail is still in regulation until the voltage drops below power-good off (POWER_GOOD_OFF). In the
case that there isn't voltage monitoring set for a given rail, that rail is considered ON if it is commanded on (either
by OPERATION command, PMBUS CNTRL pin, or auto-enable) and (TON_DELAY +
TON_MAX_FAULT_LIMIT) time passes. Also, a rail is considered OFF if that rail is commanded OFF and
(TOFF_DELAY + TOFF_MAX_WARN_LIMIT) time passes.
7.4.1.1 Turn-On Sequencing
The following sequence-on options are supported for each rail:
• Monitor only – do not sequence-on
• Fixed delay time (TON_DELAY) after an OPERATION command to turn on
• Fixed delay time after assertion of the PMBUS_CNTRL pin
• Fixed time after one or a group of parent rails achieves regulation (POWER_GOOD_ON)
• Fixed time after a designated GPI has reached a user-specified state
• Any combination of the previous options
The maximum TON_DELAY time is 3276 ms.
7.4.1.2 Turn-Off Sequencing
The following sequence-off options are supported for each rail:
• Monitor only – do not sequence-off
• Fixed delay time (TOFF_DELAY) after an OPERATION command to turn off
• Fixed delay time after deassertion of the PMBUS_CNTRL pin
• Fixed time after one or a group of parent rails drop below regulation (POWER_GOOD_OFF)
• Fixed delay time in response to an undervoltage, overvoltage, or max turn-on fault on the rail
• Fixed delay time in response to a fault on a different rail when set as a fault shutdown slave to the faulted rail
• Fixed delay time in response to a GPI reaching a user-specified state
• Any combination of the previous options
The maximum TOFF_DELAY time is 3276 ms.