English
Language : 

SR6 Datasheet, PDF (1/2 Pages) Tyco Electronics – General Purpose Relays
General Purpose Relays
Force Guided Relays
Force Guided Relay on DIN-rail SR6 Z
n 6 pole relay with force guided contacts according to EN50205
n DIN rail mounting
n AC / DC input
SCHRACK
Typical applications
contact monitoring in railway, elevator and machine controls
F0238-C
Approvals
relay SR6: VDE, UL, TUV, CQC
module SR6Z: CE
Technical data of approved types on request
Contact Data
Contact arrangement 3 form A (NO) and 3 form B (NC),
4 form A (NO) and 2 form B (NC),
5 form A (NO) and 1 form B (NC)
Rated voltage
250VAC
Max. switching voltage
250VAC
Rated current
8A
Contact material
AgSnO2,
Contact style single contact, force guided
type A according to EN 50205
Min. recommended contact load
5V, 10mA
Initial contact resistance ≤100mΩ at 1A, 24VDC
≤20Ω at 10mA, 5VDC
Frequency of operation, with/without load
6/150min-1
Contact ratings, IEC60947-5-1,
on 1 form A (NO) contact
AC15-5A
DC13-6A
Mechanical endurance
10x106 operations
Other Data
Material compliance: EU RoHS/ELV, China RoHS, REACH, Halogen content
refer to the Product Compliance Support Center at
www.te.com/customersupport/rohssupportcenter
Ambient temperature
for mounting/handling
0 to 40°C
in operation
-25 to 50°C
SR6ZC 730 only
-25 to 40°C
Terminal type screwless clamp connectors
Wire cross section
solid wire
2.5mm2
stranded wire
2.5mm2
stranded wire with bootlace crimp
1.5mm2
Mounting position
any
Weight 90g
Packaging unit
2
Dimensions
Coil Data
Coil voltage range
6 to 115 VAC/VDC,
230VAC
DC energizing voltage Urtd
6, 12, 18, 21, 24, 36, 40, 48, 60, 115VDC
AC/DC energizing voltage Urtd 24, 115VAC/VDC
AC energizing voltage Urtd 230VAC
Operative range
90 to 110% of Urtd
Release voltage (+23°C)
10% of Urtd
Max. coil power DC versions
1200mW
Max. system power AC/DC versions
2400mVA
S0423-A
Insulation Data
Initial dielectric strength
between open contacts
between contact and coil
between adjacent contacts
Clearance/creepage
between open contacts
between contact and coil
between adjacent contacts
Insulation to EN 50178, type of insulation
between contact and coil
between adjacent contacts
1000Vrms
3000Vrms
2000Vrms
microdisconnection
≥5.5/5.5mm
≥2,8 /2.8mm
reinforced
basic
Module width 46 ​mm
Module length 87 ​mm
54.0 mm (TS35)
Fit onto mounting rails according to
DIN EN ​60175
10-2012, Rev. 1012
www.te.com
© 2012 Tyco Electronics Corporation,
a TE Connectivity Ltd. company
Datasheets and product specification
according to IEC 61810-1 and to be used
only together with the ‘Definitions’ section.
1
Datasheets and product data is subject to the Datasheets, product data, ‘Definitions’ sec-
terms of the disclaimer and all chapters of
tion, application notes and all specifications
the ‘Definitions’ section, available at
are subject to change.
http://relays.te.com/definitions