English
Language : 

FCD Datasheet, PDF (1/5 Pages) TE Connectivity Ltd – Insulated safety terminals
Corcom Product Guide
Catalog: 1654001
Issue Date: 06.2011
3-phase Delta External Power Line Filter for Frequency Converters
FCD Series
UL Recognized
6FCD10
FCD Series
• Suitable to meet the latest EMC standards
• Insulated safety terminals
• Suitable for EMC troubleshooting in the field
• Very high attenuation
• High insertion loss
• BS models optimized for very high insertion loss
• BS models suitable for infeed/regenerative (ER)
applications
• Touch safe terminals provide easy connections
and prevent inadvertent contact for safety in the
most demanding applications
Ordering Information
150 FCD 10 BS -95
Terminal Block Option
-95 – 95mm terminal block
available on 150A only
omit for standard terminals
Filter Type
B – Single stage
BS – High performance
Single stage.
Omit for dual stage
Input / Output Style
10 – Terminal Block
Specifications
Maximum leakage current
voltage drop to virtual N to PE/V:
6FCD10:
12 & 16FCD10:
25, 36 & 50FCD10:
12 & 16FCD10B:
25& 36FCD10B:
50FCD10B:
80 & 110FCD10B:
150FCD10B:
180 & 230FCD10B:
FCD10BS:
.26 mA/V
.45 mA/V
.52 mA/V
.46 mA/V
.52 mA/V
.57 mA/V
.62 mA/V
.63 mA/V
.92 mA/V
3.25 mA/V
Hipot rating (one minute):
Line to Ground:
Line to Line:
2250 VDC
1450 VDC
Rated Voltage (max):
Phase to Phase:
Phase to Neutral / Ground:
480 VAC
277 VAC
Operating Frequency:
50/60 Hz
Rated Current:
6 to 230A
Operating Ambient Temperature Range
(at rated current Ir):
-10°C to +40°C
In an ambient temperature (Ta) higher than +40°C
the
maximum
operating
current (Io)
follows: Io
is calculated as
= Ir (85-Ta)/45
Electrical Schematics
6FCD10
Power line
Device
FCD Series
Current Rating
6, 12, 16, 25, 36, 50, 80, 110,
150, 180 or 230A
PE
118
Dimensions are in inches and millimeters unless otherwise specified. Values in italics
are metric equivalents. Dimensions are shown for reference purposes only.
Specifications subject to change.
PE
For email, phone or live chat, please go to
te.com/help
corcom.com