English
Language : 

408-1758 Datasheet, PDF (1/7 Pages) TE Connectivity Ltd – Crimping Dies 48752-1 through 48755-1
Crimping Dies 48752-1 through 48755-1
for AMPLI-BOND*, PLASTI-GRIP*, and
Pre-Insulated AMPOWER* Terminals
Instruction Sheet
408-1758
12 JUN 14 Rev D
Stationary Die
Wire Barrel
Crimping Die
Pin
Key
Color Code
Wire Strip
Length (Typ)
AMPLI-BOND Terminal
Insulation Barrel
Crimping Die
Socket-Head Cap Screw
PLASTI-GRIP Terminal
Moving Die
Pin Key
Color Code
Pre-insulated AMPOWER Terminal
WIRE SIZE
(AWG)
8
6
4
2
WIRE STRIP LENGTH
AMPLI-BOND TERMINALS
PLASTI-GRIP TERMINALS
MINIMUM
MAXIMUM
MINIMUM
MAXIMUM
11.51 [.453] 12.29 [.484]
11.51 [.453]
12.29 [.484]
15.47 [.609]
15.47 [.609]
16.26 [.640]
16.26 [.640]
11.51 [.453] 12.29 [.484]
TERMINAL
COLOR
CODE
Red
Blue
Yellow
Red
DIE SET
PART
NUMBER
COLOR
CODE
48752-1
48753-1
48754-1
48755-1
Red
Blue
Yellow
Red
1. INTRODUCTION
Figure 1
2. DIE INSTALLATION AND REMOVAL
This instruction sheet provides information on product
application and a maintenance and inspection
procedure for the crimping dies listed in Figure 1. The
dies are used in Hydraulic Crimping Head 69015 and
Hydraulic Hand Tool 59974-1. For detailed information
on the crimping head and hand tool, refer to the
instructions packaged with these tools.
DANGER
Avoid personal injury. Always keep fingers clear of
dies when activating power unit.
STOP
2.1. Die Insertion
These dies are designed to crimp AMPLI-BOND and
PLASTI-GRIP terminals on wire sizes 8 to 2 AWG, and
Pre-Insulated AMPOWER terminals on wire size 2
AWG. Dies are coated with a preservative to prevent rust
and corrosion. Wipe preservative from dies,
particularly from crimping areas.
NOTE
i
All dimensions in this document are in millimeters
[with inches in brackets]. Figures and illustrations
are for reference only and are not drawn to scale.
Reasons for reissue are provided in Section 6,
REVISION SUMMARY.
1. Refer to the table in Figure 1 and verify that
you have the proper die set for the terminal and
wire size being used.
2. Remove latch pin on head, then open yoke.
See Figure 2.
3. Loosen setscrew in yoke.
4. Before inserting dies in head, loosen socket
head cap screws holding insulation crimping
section of dies in place. See Figure 1. If screws
are not loosened, dies may not fit into head of
tool because of close clearance.
©2014 TE Connectivity family of companies
All Rights Reserved
*Trademark
TOOLING ASSISTANCE CENTER 1-800-722-1111
PRODUCT INFORMATION 1-800-522-6752
This controlled document is subject to change.
For latest revision and Regional Customer Service,
visit our website at www.te.com
TE Connectivity, TE connectivity (logo), and TE (logo) are trademarks. Other logos, product and/or Company names may be trademarks of their respective owners.
1 of 7
LOC B