English
Language : 

ZWQ1305224 Datasheet, PDF (1/2 Pages) TDK Electronics – 80W to 170W Quad Output Power Supplies
80W to 170W Quad Output Power Supplies
Features
u Universal Input (85 - 265VAC)
u Power Factor Corrected
u Floating Adjustable Fourth Output
u Low Profile <1U High
Key Market Segments & Applications
ZWQ Series
Specifications
Model
Input Voltage
Input Current (1)
Inrush Current (1)
Power Factor
Temperature Coefficient
Max Output Power (convection)
Max Output Power (forced air)
Overpower Protection (2)
Minimum Load
Output Voltage Accuracy
Efficiency (Typ)
Hold Up Time (1)
Leakage Current
Remote On / Off
Oper Temp (convection cooled)
Oper Temp (forced air cooled)
Storage Temperature
Humidity (non condensing)
Withstand Voltage
Isolation Resistance
Vibration (non operating)
Shock
Safety Agency Approvals
Conducted & Radiated EMI
Immunity
Weight (Typ)
Size (W x H x D)
Warranty
ZWQ80 ZWQ80 ZWQ80 ZWQ80 ZWQ130 ZWQ130 ZWQ130 ZWQ130
-5222
-5223 -5224
-5225
-5222 -5223 -5224
-5225
-
85-265VAC (47-63Hz), 120-370VDC
A
1.6 / 0.8
2.6 / 1.3
A
14/28
-
Meets EN61000-3-2
-
<0.02%/°C
W
80
130
W 104
88.7
104
104
170
149.6
170
170
W >109
>93
>109
>109
>173
>152
>173
>173
A
V1: 0.9A Conv, 1.4A Forced Air
V1: 1.5A Conv, 2.1A Forced Air
%
±5% for outputs V2 and V3
%
72
ms
20
-
0.75mA max, 0.2mA (Typ) at 100VAC / 0.44mA(Typ) at 230VAC
-
See installation manual (Not available with /A cover option)
°C
-10°C to 60°C, derate linearly to 50% load from 40°C to 60°C. (3)
°C
-10°C to 70°C, derate linearly to 50% load from 50°C to 70°C. (>30cfm airflow)(3)
°C
-30° to +85°C
-
Operating: 30 - 90% RH; Non-operating 10-95% RH
- I/P~Grnd 2kVAC (20mA), I/P~O/P 3kVAC (20mA), O/P~Grnd 500VAC (100mA) for 1 min.
-
>100M at 25°C & 70%RH, Output to Ground 500VDC
-
10 - 55Hz (1 minute sweep), 19.6m/s2 constant X, Y, Z 1 hour
-
< 196.1 m/s2
-
UL60950-1, CSA60950-1, EN60950-1, CE Mark, EN50178
-
EN55011, EN55022-B, FCC Class B, VCCI-B
-
EN61000-4-2,-3,-4,-5,-6,-8,-11
g
550
730
mm 93.5 x 35 x 210 (refer to outline drawing)
106 x 35 x 225 (refer to outline drawing)
yrs
One Year
(1) 100/200VAC
(2) Avoid prolong operation in overload
(3) /A version - additional derating, see installation manual
1-800-526-2324 • www.us.tdk-lambda.com/lp/
111
Disclaimer: us.tdk-lambda.com/lp/legal.htm