Features
u Constant Voltage / Constant Current
u Last Setting Memory
u Digital Meters
u Built-in RS232 & RS485 Interface w/ GPIB optional
u Bench or Rack Mount
u Embedded Microprocessor Controller
u Voltage up to 120V, Current up to 132A
Key Market Segments & Applications
ZUP Series
Specifications
Model
Load Regulation
Line Regulation
Recovery Time (1)
Temperature Coefficient
Temperature Drift(2)
Up programming response time
Down prog. resp. time (CV)
Down prog. resp. time (CV)
Load Regulation
Line Regulation
Temperature Coefficient
Temperature Drift(2)
Prog Voltage resolution
Prog Voltage accuracy
Prog Current resolution
Prog Current accuracy
Overvoltage Shutdown
Thermal Protection
Display - Voltage
Display - Current
Display - Status
Remote On/Off
Output Good
Voltage & Current Programming
Remote Sense
Communication Interface
Series & Parallel Operation
AC Input Voltage range
Inrush Current (100/200VAC)(3)
Hold Up Time (Typ) at 100VAC
Power Factor Correction
Temperature Range
Humidity (non condensing)
Cooling
Withstand Voltage
Isolation Resistance
Vibration & Shock (non-op.)
Safety Agency Approvals
Conducted & Radiated EMI
Warranty
ZUP6
ZUP10
ZUP20
ZUP36
ZUP60
ZUP80 ZUP120
-
2mV + 0.005% over 0 - 100% load change
-
1mV + 0.005% over 85 - 132 or 170 - 265VAC line change
ms
1ms
0.5ms
0.2ms
-
30ppm/°C following 30 minute warm up
-
0.01% + 2mV change in output
ms
50 - 60ms
80ms
120ms
ms
50ms (70ms ZUP60-14)
ms 250ms
350ms
400ms
500ms
750ms
600ms
800ms
-
0.01% + 5mA on 200W and 400W models, 0.07% + 10mA on 800W models
-
0.01% + 2mA on 200W and 400W models, 0.01% + 5mA on 800W models
-
100ppm/°C from rated current after 30 minute warm up time
-
0.02% + 5mA, 200W and 400W models, 0.05% + 10mA 800W models
-
Better than 0.028% of rated voltage
mV .02%+5mV .02%+8mV .02%+12mV .02%+20mV .02%+35mV .02%+50mV .02%+70mV
-
Better than 0.03% of rated voltage
-
0.4% + 40mA
V
0 - 7.5
0 - 13
0 - 24
0 - 40
0 - 66
0 - 88
0 - 132
-
Over temperature protected
- 3 digits (6, 20, 36, 60, 80V models), 3.5 digits (10, 120V models). Accuracy 0.2% ± 2 digits
-
3 digits, (3.5 digits 132A model). Accuracy 0.5% ± 3 digits
-
CV / CC, Alarm, Foldback, Local/Remote, On/Off
-
TTL signal or dry contact relay
-
Open Collector
-
By either Voltage (0-4V) or Resistance (0-4k)
-
Up to 0.5V compensation per output cable
-
RS232 & RS485 standard, IEEE488 optional
-
Series: Up to two units; Parallel: Up to five units in master-slave configuration
VAC
85-265VAC (47-63Hz)
A
15/30A, 200W models, 15A, 400W models, 30A, 800W models
ms
20
-
Complies with EN61000-3 Class A (0.99 typ)
-
Operating: 0 - 50°C; Storage: -20 to +70°C
-
Operating: 30 - 90% RH, Storage 10 - 95%RH
-
Internal fan
-
Input to Ground 2kVAC, Input to Output 3kVAC, Output to Ground 500VAC for 1 min.
-
>100M at 25°C & 70%RH
-
Vibration:10-55Hz(1 min.) 2G constant X, Y, Z, when correctly mounted; Shock: <20G
-
UL3111-1, EN61010-1, CE Mark
- EN55022-B conducted, A radiated, FCC Class B conducted, A radiated, VCCI-2 conducted, -1 radiated
yrs
Three Years
Notes: (1) Recovery to within +/-50mV after load change of 50-100% (2) Over 8 hour period following 30 minute warm up time
(3) 25°C ambient (cold start)
1-800-526-2324 • www.us.tdk-lambda.com/lp/
152
Disclaimer: us.tdk-lambda.com/lp/legal.htm