1200 to 2500W Front End Power Supplies
Features
u 1U High
u Up to 10,000W in 19” Rack
u Hot Swap Capable
u High Efficiency
u Full array of signals
Key Market Segments & Applications
TH Series
Specifications
Model
Nominal Voltage
V
Output Voltage Range
VDC
Total Regulation
%
Output Current
A(max)
Current limit
(1) A
Short Circuit Current
%
Output Noise
mV
Output Rise Time
ms
Dynamic Response
%
Overvoltage Protection
(1) VDC
Load Sharing
%
I2C Programing
-
Signals (opto isolated)
(4) -
Remote On/Off
V
Auxiliary Output
(3) -
AC Input
VAC
Input Frequency
Hz
Power Factor
-
Inrush Current
(2) A
Efficiency (at full load)
%
Immunity
-
EMC (conducted and radiated) -
Operating Temperature
°C
Storage Temperature
°C
Humidity
%
Altitude
ft
Shock
G
Vibration
Hz
Safety Agency
-
Size (L x W x H)
in.
Weight
lbs
Warranty
yrs
TH120012(5)
TH120024
TH120048
TH250048(5)
12
24
48
48
10.5-14
21-28
42-56
42-56
±1%
100
50
25
50
120
60
30
60
150
75
37
75
250mV peak to peak (10kHz to 20MHz)
100-400 ms
3% in 10ms for a 10-100% load change
13-15
27-30
50-60
50-60
±5%
Set output Volt, Monitors AC present, Converter OK, Thermal Profile, Fan fail
AC Fail, Module Alarm, Temp Alarm
Shuts down outputs by applying 3.3 to 5V
12V@100mA
90-264
90-264
90-264
180-264
47-63
0.99 typ. @ 230VAC, full load, meets EN61000-3-2
30 Amps peak
88
90
92
93
EN61000-4-2,-3,-4,-5,-6,-8,-11
EN55022, Level B, FCC Class B
-40 to 70, derate linearly to 60% load above 50°C
-40 to 85
5 to 95 (non-condensing)
-200 to 8000
IEC68-2-27, Mil-STD-810E, 20G
IEC68-2-64 (random) 20-2000Hz, 30 minutes
UL60950, CSA 22.2 No. 60950-00, EN60950, CE Mark
14.25 x 4.00 x 1.69 (stand alone), 16.30 x 17.31 x 1.7 (THR4 Rack)
Power Module 6lbs, Rack 9lbs
Two Years
1 Adjustable via i2C or through Lambda Network Interface Card
2 Excludes Xcaps in the EMC input filter
3 Output operates independent of main DC output and is referenced to (-)Vout
4 All three signals share a common return - logic ground
5 Use rack model THR400
1-800-526-2324 • www.us.tdk-lambda.com/lp/