English
Language : 

RTW28-3R6C Datasheet, PDF (1/2 Pages) TDK Electronics – Single Output Industrial Power Supplies
Single Output Industrial Power Supplies
Features
u 5 Year Warranty
u Ultra Thin Package
u SEMI F47 Compliant (high line AC)
u Universal Input (85 - 265VAC)
u High Efficiency
u Wide range AC Input
Key Market Segments & Applications
RTW Series
Specifications
Model
Input Voltage range
(1)
Input Current (100/200VAC) (Typ) A
Inrush Current (100/200VAC)
A
Power Factor
-
Overcurrent Protection
-
Overvoltage Protection
V
Hold Up Time (100/200VAC)
ms
Leakage Current (max at 240VAC) mA
Load Regulation
%
Line Regulation
%
Remote Sense
-
Current Share
-
Remote On/Off
-
DC Fail Signal
-
Indicator
-
Operating Temperature
-
Storage Temperature
°C
Humidity (non condensing)
-
Cooling
-
Withstand Voltage
-
Isolation Resistance
-
Vibration (non operating)
-
Shock (Vertical mounting) (3) -
Safety Agency Approvals
-
Line Dip
-
Conducted & Radiated EMI
-
Immunity
-
Weight (Typ)
g
Size (WxHxD)
in
Warranty
yr
50W
100W
150W
300W
85 - 265VAC (47 - 440Hz), 120-370VDC
0.7 / 0.4
1.5 / 0.75
1.9 / 1.0
2.0 / 4.0
14 / 28
15 / 30
Meets EN61000-3-2
Yes, typically 105 - 125% (100 & 150W hiccup style)
Yes, typically 120-140%. Cycle input to reset
>20
0.6
0.45
0.65
0.75
0.4% (0-100% load change)
0.2% (85-132 or 170-265VAC line change)
Yes
No
Yes
Yes, see instruction manual on website
No
Yes
Green LED = ON
-10°C to +71°C, -20°C start up. See derating curves on website technical downloads
-30 to +75°C
10 - 95%RH
Convection
Input to Ground 2kVAC, Input to Output 3kVAC, Output to Ground 500VAC for 1 min.
>100M at 25C & 70%RH, Output to Ground 500VDC
5 - 200Hz (10 min sweep), 19.6m/s2, 1 hour (Amplitude 10mm)
196m/s2
588m/s2
UL60950-1, CSA60950-1 (cUL), EN60950-1, CE Mark
Complies with SEMI F47 (200VAC line only)
EN55011 / EN55022-B, FCC-B
IEC61000-4-2 (Level 4), -3, -4 (Level 3), -5 (Level 4)
290
450
600
1300
0.87x3.23x4.88
0.98x3.23x6.3
1.18x3.62x7.09
1.57x4.72x9.84
Five Years
(1) Safety approvals do not cover DC input
(2) 100/200VAC
(3) Non operating, 11 ±5ms, 3 directions, 3 times each.
See website technical downloads for detailed information
1-800-526-2324 • www.us.tdk-lambda.com/lp/
120
Disclaimer: us.tdk-lambda.com/lp/legal.htm