English
Language : 

NV1453FF Datasheet, PDF (1/2 Pages) TDK Electronics – 3 x 5 175-200W Power Supplies
3” x 5” 175-200W Power Supplies
Features
 1-5 Outputs
 Up to 90% Efficient
 Active Power Factor Correction
 Universal Input (90 - 264VAC)
 No Minimum Loads
 Medical Approvals (Basic Insulation Input-Output)
Key Market Segments & Applications
NV175 Series
Specifications
Model
NV175
Input Voltage range
-
90 - 264VAC (47 - 63Hz, 440Hz with reduced PFC)
Inrush Current
A
<40A at 25°C and 264VAC input, Cold Start
Power Factor Harmonics
-
EN61000-3-2 Compliant (0.97 typical)
Regulation Total
- 1%; Including Line (for 90-264VAC input change), Load (for 0-100% load change) and
Cross (for 0-100% load change on any other output) regulation
Ripple & Noise
mV
1% or 50mV (Which ever is greater)
Efficiency
-
Up to 90%, configuration dependant
Minimum Load
A
None
Overcurrent Protection
-
>105%
Overvoltage Protection
V
CH1 & CH2, 120-130%, Cycle AC line to reset
Overtemperature Protection
-
Yes
Hold Up Time (Typ)
ms
>16ms at 90VAC Input
Leakage Current (max)
μA 123μA 120VAC 60Hz, 257μA 240VAC 60Hz, <300μA 264VAC 63Hz (Type Test results)
Remote Sense
-
On Outputs CH1 & CH2, 0.5V compensation maximum
DC Good
-
CH1 Only, High on Fail (90% of nominal ±5%)
Remote On/Off (Specify N option) - -N1 or -N2 option: TTL level high = Off, -N3 or -N4 option: open circuit = Off (except standby)
Operating Temperature
(1)(7) -
0 to +70°C. Derate linearily to 50% load from 50°C to 70°C
Storage Temperature
-
-40 to +85°C
Humidity (non condensing)
-
5 - 95% RH
Cooling
-
Forced air, 2m/s from input to output (Approx 10 CFM)
Isolation
(4) -
Input to Ground 2.3kVDC, Input to Output 4.3kVDC, Output to Ground 200VDC
Vibration (non operating)
-
Conforms to MIL-STD-810E, Method 516.5, Pro I, IV, VI; EN60068-2-6, IEC68-2-6
Shock
-
Conforms to MIL-STD-810E/F, Method 514.4, Pro I, Cat 1,9; EN60068-2-27,
EN60068-2-47, IEC68-2-47, IEC68-2-47, JIS C0041-1987
Safety Agency Approvals
-
UL/CSA/IEC/EN 60950-1, UL/CSA/IEC/EN 60601-1, ANSI/AAMI ES60601-1,
IEC/EN 61010-1, CE Mark
Immunity
-
EN61000-6-2:2001, EN61000-4-2, -3, -4, -5, -6, -8, -11
Conducted Emissions and Flicker
-
EN55022 Class B (per CISPR.22), EN61000-3-3
Radiated Emissions
(2) -
EN55022 Class A (per CISPR.22)
Weight (Typ)
g
250g
Size (without cover)
(3) in
3” x 5” x 1.25”; N option version 3.7” x 5” x 1.25”
Warranty
yrs
Three Years
(1) -20°C cold start
(2) See application note for Class B
(3) Including underside component leads
(4) Input-Output: Reinforced IEC60950-1, Basic IEC 60601-1.
See NV175-M for reinforced medical insulation
1-800-526-2324 • www.us.tdk-lambda.com/lp/
81
Disclaimer: us.tdk-lambda.com/lp/legal.htm