English
Language : 

HWS1500-24-HD Datasheet, PDF (1/2 Pages) TDK Electronics – Single Output Industrial Power Supplies
HWS50-1500/HD Series
Single Output Industrial Power Supplies
Features
u Limited Lifetime Warranty
u -10 to +71°C Operation (-40°C start up)
u Universal Input (85 - 265VAC)
u Conformally coated pcbs
u Class 1 Div 2 option (/RYHD suffix)
u Wide range AC Input
Key Market Segments & Applications
Specifications
Model
HWS50 HWS100 HWS150 HWS300 HWS600 HWS1000 HWS1500
Input Voltage range (47-63Hz)
-
85-265VAC or 120-370VDC
85-265VAC or 120-330VDC (No DC input for HWS1500)
Input Current (Typ)
(1) A 0.7 / 0.35 1.3 / 0.65 1.9 / 0.95 4.1 / 2.1 8.1 / 3.9 13.5 / 7 19 / 10
Inrush Current
(1) A
14 / 2
20 / 4
Power Factor
-
Meets EN61000-3-2
Temperature Coefficient
-
<0.02%/°C
Overcurrent Protection
-
>104%
Overvoltage Protection
V
Yes (See table on page 2)
Hold Up Time (Typ)
ms
20
Leakage Current (60Hz)
mA
<0.5mA
<0.75mA
<1.2mA ≤1.5mA
Remote Sense
-
No
Yes
Indicator
-
Green LED = ON
Remote On/Off
-
No
Yes (Isolated from output)
Parallel operation
-
No
Single wire connection (5 units max)
DC Good
-
No
Yes
Remote Adjust (PV)
-
No
Yes (3)
Operating Temperature
°C
HWS50-150: -10°C to +71°C, (-10 ~+50°C: 100%, +60°C: 60%, +71°C: 20%)
and Derating (operation to
HWS300-1500: -10°C to +71°C, (-10 ~+50°C: 100%, derate linearly to 50% load from +50 to +71°C)
+74°C - contact factory)
Guaranteed start up at -40°C (see specification sheets on website for details and derating)
Storage Temperature
°C
-40 to +85°C
Humidity (non condensing)
-
Operating: 30 - 90%RH (10 -90% on HWS300-1500), Non operating 10 - 95%RH
Cooling
-
Convection
Internal fan
Withstand Voltage
(2) -
Input to Ground 2kVAC, Input to Output 3kVAC, Output to Ground 500VAC for 1 min.
Isolation Resistance
- >100MΩ at 25°C & 70%RH, Output to Ground 500VDC, >10M Output to remote on/off 100VDC
Vibration (non operating)
-
MIL-STD-810F 514.5 Category 4, 10 (HWS1500 Cat 4, figure 514.5C-1)
Shock (in packaging)
-
MIL-STD-810F 516.5 Category I, VI (HWS1500 <196.1m/s2)
Safety Agency Approvals
-
UL60950-1, CSA60950-1, EN60950-1, EN50178, CE Mark
Line Dip
-
Complies with SEMI F47 (200VAC line only)
Conducted & Radiated EMI
-
EN55011 / EN55022-B, FCC-B, VCCI-B (HWS1500 Class A)
Immunity
-
IEC61000-4-2 (Level 2,3), -3, -4, -6, (Level 3), -5, -8 (Level 4), -11
Weight (Typ)
g
280
450
500
1000
1600
3200
3800
Size (WxHxD)
in 1.04x3.23x4.72 1.1x3.23x6.3 1.46x3.23x6.3 2.4x3.23x6.5 3.94x3.23x6.5 5x3.2x9.5 5x3.25x11
Warranty
yrs
Limited lifetime warranty (See TDK-Lambda’s terms & conditions)
(1) 100/200VAC input
(2) HWS300-600 2.5kVAC Input to ground
(3) 1-6V program voltage input to adjust output 20-120% (typical) of
nominal. See instruction manual for details & models with this feature.
(*) Class 1 Div 2 option (/RYHD suffix
1-800-526-2324 • www.us.tdk-lambda.com/lp/
63
Disclaimer: us.tdk-lambda.com/lp/legal.htm