MDL Datasheet, PDF (2/2 Pages) Systemsensor advanced ideas. – Sync Circuit Module
Sync•Circuit™ Module Specifications
Architectural/Engineering Specifications
Synchronization Circuit Module shall be a System Sensor Sync•Circuit Model _________ listed to UL464 and shall be approved for fire protective service. The
module shall synchronize SpectrAlert® strobes at 1 Hz and horns at temporal 3. Also, the module shall be capable of silencing the horns on horn/strobe models,
while operating the strobes, over a single pair of wires. The module shall be capable of mounting to a 411⁄16˝× 411⁄16˝× 21⁄8˝ back box and shall control two Style Y
(class B) or one Style Z (class A) circuit. The module shall be capable of multiple zone synchronization by connecting multiple modules together via a slave-in/
slave-out arrangement and re-synchronizing each other along the chain. Note: The module shall not operate on a coded power supply.
Physical Specifications
Dimensions
51⁄4˝ L × 51⁄4˝ W
Mounting
411⁄16˝ × 411⁄16˝ × 21⁄8˝ back box
Indoor Operating Temperature
32° to 120° F (0° to 49° C)
Electrical/Operating Specifications
Operating Voltage
12 or 24 VDC and FWR unfiltered
Operating Voltage Range (12 V)
Operating Voltage Range (24 V)
Maximum Load on Loop
U.S. Patent Nos.
9 to 17.5 VDC
17 to 33 VDC
3 Amps/zone
5,5H98O,1R3N9 S SILENCED OVER TWO WIRE CIRCUIT
5,8MT5O0A,S1IN7TT8EERRMROUDPTUALBELHEOPRONWCEORNSTOROURLCCEONNECTS
Horns and Chimes Silenced Over Two-Wire Circuit
1. Any mix of Horn/Strobes, Chime/Strobes or Strobe only devices is acceptable
2. Horn and chime control connects to interruptible power source
FACP #1
(+)
NAC1
(–)
(+)
NAC2
(–)
(+)
NAC3
(–)
EOL
MASTER MODULE
}(+) HORN
(–) CONTROL
ZONE 1
OUT
}(+) ZONE 1
(–) IN
ZONE 2
OUT
}(+) ZONE 2
(–) IN
SYNC
ERROR
}(+) SLAVE
(–) IN
SLAVE
OUT
TO NEXT
SPECTRALERT
DEVICE OR
EOL
TO NEXT
SPECTRALERT
DEVICE OR
EOL
FACP #2
(+)
NAC1
(–)
(+)
NAC2
(–)
TEMP JUMPER OFF
SLAVE MODULE
} HORN
CONTROL
ZONE 1
OUT
}(+) ZONE 1
(–) IN
ZONE 2
OUT
}(+) ZONE 2
(–) IN
SYNC
ERROR
}(+) SLAVE
(–) IN
SLAVE
OUT
TEMP JUMPER OFF
TO NEXT
SPECTRALERT
DEVICE OR
EOL
TO NEXT
SPECTRALERT
DEVICE OR
EOL
All SpectrAlert horns,
horn/strobes, and strobes
will operate in sync.
Current Draw and Ordering Information
Average Current (mA)
Red
White
Voltage
DC
FWR
MDL,
MDLW,
12
10
12
MDLA (Canadian) MDLWA (Canadian) 24
11
15
Peak Current (mA)
DC
FWR
30
31
35
37
In-rush Current (mA)
DC
FWR
87
122
198
262
3825 Ohio Avenue • St. Charles, IL 60174
Phone: 800-SENSOR2 • Fax: 630-377-6495
©2007 System Sensor.
Product specifications subject to change without notice. Visit systemsensor.com for
current product information, including the latest version of this data sheet.
A05-1007-005 • 6/07 • #1676