English
Language : 

SENS-RDR Datasheet, PDF (1/2 Pages) Systemsensor advanced ideas. – Sensitivity Reader
i3™ Series
Sensitivity Reader
System Sensor’s i3 series sensitivity reader displays
sensitivity and status indication readings of all i3 series
detectors and other compatible System Sensor
smoke detectors.
Sensitivity readers, voltmeters and multimeters are designed
to assure smoke detectors are working within their listed and marked
sensitivity ranges.
Features
• An LCD screen that displays sensitivity by percent-per-foot
obscuration
With the System Sensor i3 series sensitivity reader (SENS-RDR),
an LCD screen displays a detector’s exact sensitivity by percent-
per-foot obscuration. Therefore, unlike many sensitivity readers,
voltmeters and multimeters that display only the voltage rating, the
step of cross-referencing a voltage reading to a sensitivity range is
eliminated with the SENS-RDR. Beyond displaying the sensitivity
reading, the LCD screen indicates the status of the detector in alpha-
numeric text as GOOD, SERVICE or REPLACE.
• Connectors for a hand-held device or threaded extension pole
• Dual LED and sounder indicators
• A low battery indicator
• Automatic shut-off after 30 minutes
Testing a detector’s sensitivity is a simple and quick task. The
SENS‑RDR connects to hand-held devices and threaded extension
poles for those detectors installed out of reach, eliminating the need
for a ladder. Within 10 seconds, the dual LED and sounder will alert
the installer that the reading has been taken. With dual indicators,
the installer won’t have to rely on a single LED in areas with visibility
issues or a single sounder in areas with audibility issues.
The SENS-RDR operates with two AA alkaline batteries. To ensure
these batteries are operable, the SENS-RDR has a low battery
indicator. And, to maximize battery life, the SENS-RDR automatically
shuts off after 30 minutes.
Agency Listings