RTC100 Datasheet, PDF (1/2 Pages) Systemsensor advanced ideas. – Remote Test Coil Kit for use
INSTALLATION AND MAINTENANCE INSTRUCTIONS
RTC100 Remote Test Coil Kit for use with the
Low Profile B114LP and B114LPBT Bases
Specifications
Dimensions:
RTS451 Power Requirements
Alarm LED:
Test Coil:
Total Current:
Test Switch:
Reset Switch:
Alarm Response Time:
Operating Temperature Range:
Humidity:
6.1″ diameter flanged base
1.66″ high
2.8 – 32 VDC, 10 mA max.
15.5 – 32 VDC, 95 mA max.
105 mA max.
10 VA @ 32 VDC
10 VA @ 32 VDC
40 seconds max.
–10°C to 60°C (14°F to 140°F)
10 to 95% RH, noncondensing
3825 Ohio Avenue, St. Charles, Illinois 60174
1-800-SENSOR2, FAX: 630-377-6495
NOTICE: This manual should be left with the owner/user Figure 1:
of this equipment.
General Description
The System Sensor Model RTC100 Remote Test Coil Kit al-
lows for the remote testing of duct smoke detectors using
the B114LP (120 VAC) or B114LPBT (24 VAC/DC) bases
when installed in inconvenient or difficult-to-reach loca-
tions. Model RTC100 can be installed in almost any conve-
nient location and can be attached to a standard 2″ × 4″
electrical box.
The National Fire Protection Association has published
standards and practices for the installation and use of this
device. As a result, System Sensor recommends that the
installer be familiar with these standards and practices,
local codes, and any special requirements of the authority
having jurisdiction.
RTC100 Contents
1 RTS451 Remote Test Station
1 Test Coil Replacement Ring
1 Screw Pack (2 mounting Assembly screws)
1 Jumper with spade lugs
1 M02-04 Test Magnet
Installation
Installation of the Model RTC100 consists of attaching the
test station to the mounting surface, mounting the test coil
replacement ring on the detector, and routing the necessary
wiring between them. This installation procedure assumes
that the associated detector base is already installed and
ready for operation.