LFD30-2 Datasheet, PDF (1/2 Pages) Systemsensor advanced ideas. – Low Flow Rate Waterflow Detectors
Accuflow™ Series
Low Flow Rate
Waterflow Detectors
Models Available
LFD20
LFD25-73MM
LFD25-76MM
LFD30-2
LFD40
Replacement Parts
WFDW
Cover wrench
546-9000
Cover tamper
switch kit
WFDN4
Gasket kit
LFD30-2
LFD30-2 (cover removed)
Product Overview
For use in wet pipe water mist systems
Compatible with 2 to 4 inch stainless
steel and brass pipe
Solid state retard assures precise
timing accuracy
System Sensor’s Accuflow™ Low Flow Rate detectors are a new line of solid state
waterflow detectors designed for use in wet pipe water mist systems where low
flow detection is required.
Robust Construction. Accuflow low flow detectors consist of a rugged enclosure for
indoor and outdoor use. Like all System Sensor waterflow detectors, low flow models
operate across a wide temperature range, from 32ºF to 120ºF (0°C to 49°C).
Dipswitch selections simplify
retard settings
Non-polarized, two-wire design
allows connection to a local bell and
conventional or addressable systems
NEMA 4 rated
Reliable Performance. Accuflow low flow detectors are intended for applications
where flow detection of 3 GPM or greater is required. By incorporating a solid state
retard, proper sensitivity, timing accuracy and switch resetting is assured.
False Alarm Immunity. The solid state circuitry of Accuflow low flow detectors
provides greater timing accuracy over traditional mechanical retard designs. This
accuracy minimizes the risk of false alarms created by pressure surges or air trapped
within the sprinkler system.
Synchronized switches activate
both the alarm panel and local
bell simultaneously
Simplified Operation. Accuflow low flow detectors are designed to simplify installa-
tion. Wired like traditional waterflow detectors, these models do not require the
installer to run an additional third wire. Two conduit openings permit easy attach-
ment to the local alarm system.
®