CO1224 Datasheet, PDF (1/2 Pages) Systemsensor advanced ideas. – Carbon Monoxide Detector
CO1224
Carbon Monoxide
Detector
System Sensor’s CO1224 provides early warning when
its electrochemical sensing technology accurately
measures carbon monoxide levels in the air.
Carbon monoxide is an odorless, colorless, tasteless and highly
toxic gas that is produced when fuels, such as wood, gasoline,
charcoal and oil, are burned with insufficient air. The majority of
residential and commercial fatalities caused from these fuels come
from heating systems, power tools and charcoal grills.
Features
• Full compliance with UL 2075
• A code required trouble relay
• Wiring supervision with SEMS terminals
If carbon monoxide is detected, the CO1224 will alert residents
by sounding and flashing a temp-4 signal alarm. Protection is
guaranteed 24/7 by a central station, regardless of whether residents
are away from home, sleeping or already suffering from the effects
of CO.
• A six-year end-of-life timer
• 12/24 VDC
• A current draw of 20mA in standby and 40mA in alarm
• Versatile mounting for wall and ceiling
• Electrochemical sensing technology
The CO1224 is specifically designed for system operation. This means
the detector is fully listed to UL 2075, offering a code required
trouble relay, which sends a sensor failure or end-of-life signal to
the control panel and the central station, as well as SEMS-type
terminal Philips-head screws, which provide a quicker and more
positive wiring connection and code required wiring supervision.
Also, the CO1224 offers a low current draw, allowing more detectors
to be connected to the panel without having to purchase a more
expensive panel or an extra power supply.
Because the CO1224 is a 12/24 VDC detector, it will operate on most
industry security or fire alarm control panels.
Agency Listings
2075
5276-1653:194
454-06-E