English
Language : 

CHR Datasheet, PDF (1/4 Pages) Systemsensor advanced ideas. – Selectable Output Chimes and Chime/Strobes
Selectable Output
Chimes and Chime/Strobes
SpectrAlert® Advance selectable-output chimes and
chime/strobes are rich with features guaranteed to cut
installation times and maximize profits.
SpectrAlert Advance selectable-output chimes and chime/
strobes are private mode notification appliances used to alert trained
personnel to investigate possible emergency situations and to take
appropriate action. Security guard and nurse workstations are ideal
locations for chime products.
Features
• Plug-in design
• Shorting spring on mounting plate for pre-installation continuity
check
SpectrAlert Advance chimes and chime/strobes are rich with
features guaranteed to cut installation times and maximize profits.
The SpectrAlert Advance Series of notification appliances is designed
to simplify your installations, with features such as plug-in designs,
instant feedback messages to ensure correct installation of individual
devices, and seven field-selectable candela settings for chime/
strobes.
• Captive mounting screw
• Torx screw for tamper resistance
• Field-selectable candela settings: 15, 15/75, 30, 75, 95, 110, 115
• Automatic selection of 12- or 24-volt operation at 15 and 15/75
candela
• Minimal intrusion into the back box
More specifically, when installing SpectrAlert Advance products, first
attach a universal mounting plate to a four-inch square, four-inch
octagon, single-gang, or double-gang junction box. Then, connect
the notification appliance circuit wiring to the SEMS terminals on the
mounting plate.
• Rotary switch for tone selection
• Two volume settings
• Electrically compatible with existing SpectrAlert products
• Listed for ceiling or wall mounting
Finally, attach the chime or chime/strobe to the mounting plate by
inserting the product’s tabs in the mounting plate’s grooves. The
device is rotated into position, locking the product’s pins into the
mounting plate’s terminals. The device will temporarily hold in place
with a catch until it is secured with a captive mounting screw.
SpectrAlert Advance products allow you to choose:
• 12 or 24 volts
• At 24 volts, 15, 15/75, 30, 75, 95, 110, or 115 candela by way of rear-
mounted slide switch and front view window
• Select chime tones and volume using a simple rotary switch
Agency Listings
S4011
3023572
MEA452-05-E
7125-1653:188 (chime/strobes)
7125-1653:189 (chimes)