B110RLP Datasheet, PDF (1/4 Pages) Systemsensor advanced ideas. – Plug-in Detector Base
INSTALLATION AND MAINTENANCE INSTRUCTIONS
B110RLP Plug-in Detector Base
For use with the following smoke detectors:
In US :
1151, 2151
In Canada: 1151A, 2151A
In Europe: 1151E, 2151E
3825 Ohio Avenue
St. Charles, Illinois 60174
1-800-SENSOR2, FAX: 630-377-6495
Specifications
Base Diameter:
6.2 inches (157 mm)
Base Height:
0.95 inches (24 mm)
Weight:
0.3 lb. (130 g)
Mounting:
4-inch square box with or without plaster ring. Min. Depth–1.5 inches
4-inch octagon box. Min. Depth–1.5 inches
3-1/2 inch octagon box. Min. Depth–1.5 inches
Operating Temperature Range: 0° to +49°C (32° to 120°F)
Operating Humidity Range:
10% to 93% Relative Humidity
Electrical Ratings — includes base and detector
System Voltage:
24 VDC
Maximum Ripple Voltage:
4 Volts peak to peak
Start-up Capacitance:
0.02 µF Maximum
Standby Ratings:
17 VDC Minimum; 32 VDC Maximum
120 µA Maximum
Alarm Ratings:
10 mA Minimum at 10.5 VDC; 62 mA Maximum at 32 VDC
(If used, the RA400 remote lamp operates within specified detector alarm currents.)
Maximum Alarm Impedance:
1050Ω
Minimum Alarm Impedance:
516Ω
Reset Voltage:
2.50 VDC Minimum
Reset Time:
0.3 Seconds Maximum
Start-up Time:
34.0 Seconds Maximum
Before Installing
Please thoroughly read the System Sensor manual I56-407,
Guide for Proper Use of System Smoke Detectors, which pro-
vides detailed information on detector spacing, placement,
zoning, wiring, and special applications. Copies of this
manual are available at no charge from System Sensor. (For
installations in Canada, please refer to CAN4-S524,
Standard for the Installation of Fire Alarm Systems, and
CEC Part 1, Sec. 32.)
NOTICE: This manual should be left with the owner/user
of this equipment.
IMPORTANT: The detector used with this base must be
tested and maintained regularly following NFPA 72 require-
ments. The detector used with this base should be cleaned
at least once a year.
General Description
The B110RLP plug-in detector base is used with System
Sensor model 1151 and 1151A ionization detector heads and
model 2151 and 2151A photoelectronic detector heads. The
capability of plugging these detectors into a variety of spe-
cial bases makes them more versatile than equivalent
direct-wired models. Refer to the System Sensor catalog for
other available plug-in detector bases.
This base is intended for use in 2-wire systems, with screw
terminals provided for power, ground, and remote annun-
ciator connections. The base also contains a resistor to pro-
vide current limiting in the alarm state.
D150-04-00
1
I56-596-03R