English
Language : 

5251P Datasheet, PDF (1/4 Pages) Systemsensor advanced ideas. – Intelligent Plug-In Model Fixed Temperature Sensor
INSTALLATION AND MAINTENANCE INSTRUCTIONS
Intelligent Plug-In Model 5251P
Fixed Temperature Sensor
A Division of Pittway
3825 Ohio Avenue, St. Charles, Illinois 60174
1-800-SENSOR2, FAX: 630-377-6495
Before installing sensors, refer to NFPA 72, and 101 (Life Safety Code) for information on sensor spacing, placement, zon-
ing, and special applications.
GENERAL DESCRIPTION
Model 5251P is an intelligent sensor that utilizes a state-of-the-art thermistor sensing circuit for fast response. This sensor
is designed to provide open area protection with 50 foot spacing capability and is intended for use with compatible con-
trol panels only.
Two LEDs on each sensor light to provide 360° visibility of the sensor indication. The LEDs can be latched ON by code
command from the panel for an alarm indication. The LEDs can also be unlatched to the normal condition by code com-
mand. Remote LED annunciator capability is available as an optional accessory (Part No. RA400Z).
SPECIFICATIONS
Diameter:
Height:
Weight:
Installation Temperatures:
Operating Humidity Range:
Mounting:
Voltage Range:
Standby Current:
LED Current:
Fixed Temperature Rating:
6.1 inches (155 mm) installed in B210LP
4.1 inches (104 mm) installed in B501
2.0 inches (51 mm)
5 ounces (150 gm)
-4° F to 100° F (-20° C to 38° C)
10% to 93% Relative Humidity Non-condensing
B210LP flanged base
B501 flangeless base
B501 with RMK400 recessed mounting kit
15 to 32 Volts DC Peak
300 µA @ 24 VDC (one communication every 5 seconds with LED blink enabled)
6.5 mA @ 24 VDC
135° F (57° C)
WIRING GUIDE
Refer to the installation instructions for the particular plug-in base being used: 1) for the B210LP base (D250-01-00); 2) for
the B501 base (D550-02-00); 3) for the RMK400 used with the B501 base (D450-07-00). Bases are provided with screw ter-
minals for power, ground, and remote annunciator connections. See Figure 1.
D200-88-00
1
I56-1331-02R