2100TR Datasheet, PDF (1/4 Pages) Systemsensor advanced ideas. – Photoelectronic Smoke Detector with Fixed Heat
INSTALLATION AND MAINTENANCE INSTRUCTIONS
2100TR Photoelectronic Smoke
Detector with Fixed Heat
3825 Ohio Avenue, St. Charles, Illinois 60174
1-800-SENSOR2, FAX: 630-377-6495
Figure 1. Wiring diagram for the 2100TR detector:
IMPORTANT: OBSERVE POLARITY
Polarity must be observed on the remote annunciator connections.
+
INITIATING
LOOP –
EOL
UL LISTED
COMPATIBLE
CONTROL
PANEL
+
–
RA400Z
REMOTE
ANNUNCIATOR
NC
(OPTIONAL) COMMON
RELEASING
DEVICE
NO
OPTIONAL CLASS A WIRING
+P
+W
–R
A+
A-
NC A
CU
NO X
NOTE: ONLY ONE DETECTOR PER ZONE CAN BE USED.
A78-2336-17
Specifications
Diameter:
Height (including mounting bracket):
Weight:
Operating Temperature Range
Operating Humidity Range:
Latching Alarm:
Heat Sensor:
Electrical Ratings
System Voltage (nominal):
Minimum:
Maximum:
Maximum Ripple Voltage:
Standby Current:
Alarm Ratings:
Reset Voltage:
Reset Time:
Start-up Time:
EOL Relay:
Remote Annunciator Output:
Auxiliary Relay Contact Ratings:
Resistive Load:
Special Considerations:
5.5 inches (140 mm)
1.7 inches (43 mm)
6.8 oz. (190 g)
32° to 100° F (0° to 38° C)
10% to 93% Relative Humidity, Noncondensing
Reset by momentary power interruption
135° F Fixed Temperature Electronic Thermistor
12 or 24 VDC
8.5 VDC
35 VDC
30% of nom. Voltage (peak to peak)
50 µA average, 100 µA maximum
25.5 mA minimum, 100 mA maximum
(Alarm current must be limited to 100mA by the control panel. If used, the RA400Z
Remote Annunciator operates within the specified detector alarm currents.)
1.3 VDC minimum
0.3 seconds maximum
30 seconds maximum (after 60 sec. reset)
A77-716B, 12/24 VDC
7 mA maximum
1A @ 30 VAC
1A @ 30 VDC
Only one detector can be used per zone.
D200-68-00
1
I56-1144-05R