English
Language : 

AQ0400IUXX Datasheet, PDF (2/14 Pages) SynQor Worldwide Headquarters – Parallel operation supported
Technical Specification
AC Input: 85-264 Vrms
DC Output: 12/24/36/48 V Semi-reg.
Power: 400 W
Grade: Industrial
ACuQor 400W Series Electrical Characteristics
All specifications typical with TA = 25 °C, unless otherwise specified. Specifications subject to change without notice.
MAIN OUTPUT SPECIFICATIONS
Output power (continuous) 85-132/170-264 Vrms
(5 s transient)
85-132/170-264 Vrms
132-170 Vrms
400 W
500 W
See Figures 10
GENERAL SPECIFICATIONS
Fundamental ripple freq. Input
Output
Audible noise
Fan speed varies with temp.
500 kHz
250 kHz
39 dBA @ 1 m max.
Nominal DC output
voltage (at 250W)
(Semi-regulated)
Efficiency
(see figs. 3 - 10)
Hold-up time (to -20%)
12 Vout
24 Vout
36 Vout
48 Vout
12 Vout, 115 Vrms, 400 W
48 Vout, 115 Vrms, 400 W
12 Vout, 230 Vrms, 400 W
48 Vout, 230 Vrms, 400 W
12 Vout
24 / 36 / 48 Vout
12.4 V
25 V
37.5 V
50 V
88% typ.
90% typ.
89% typ.
91% typ.
16 ms @ 400 W
20 ms @ 400 W
Weight (EA \ EC)
(SC \ RC)
(UC \ TC)
MTBF
MIL-217
Demonstrated
ISOLATION SPECIFICATIONS
Isolation voltage
Input to output
Input to ground
Output to ground
343 g (12.1 oz) \ 446 g (15.7 oz)
846 g (29.8 oz) \ 879 g (31 oz)
1224 g (43.2 oz) \ 1298 g (45.8 oz)
343.6 kHours
TBD kHours
3000 Vrms
1500 Vrms
500 Vrms
Maximum load capacitance 12 Vout
24 Vout
36 Vout
48 Vout
Output ripple voltage
Switching frequency (20 MHz BW)
Twice line frequency (at 300W)
16,000 µF
8,000 µF
4,000 µF
2,000 µF
0.5% p-p
5.0% p-p
Insulation resistance
Leakage currents
Output to ground
ENVIRONMENTAL CHARACTERISTICS
Thermal performance
Operating ambient (see Figure 2)
Non-operating ambient
Relative humidity
Non-condensing
10 MΩ min.
See Note 2
-40 ºC to +70 ºC
-40 ºC to +85 ºC
5-95% RH
Turn-on delay
Transient response
Overvoltage protection
Short circuit protection
Total regulation
Auxillary Output
Thermal protection
REMOTE_ENABLE
Iout steps from 50-75%
At 0.2 A/µs
Cyclic restart
Cyclic operation
Over line, load and temperature
Always on (See Note 1)
Automatic recovery
Input Low Voltage
Input High Voltage
INPUT SPECIFICATIONS
AC input voltage
Input frequency
Input current
Power factor
Universal range
115 Vrms @ 400 W
230 Vrms @ 400 W
2 s max.
3% typ / 6% max. dev.
100 ms recovery
110-120%
115% rated Iout
±6.0%
5 V @ 50 mA
+125 ºC (PCB Temp)
0.45 V (max)
4.15 V (min)
Altitude
Random vibration
Shock
Operating
Non-operating
5-500 Hz
Half-sine, 10 ms, 3 axes
EMC CHARACTERISTICS
Conducted emissions
EN55011 and EN55022, FCC
part15
Line frequency harmonics EN61000-3-2
Voltage fluctuations
EN61000-3-3
ESD air
EN61000-4-2
ESD contact
EN61000-4-2
85-264 Vrms
47-63 Hz
4 Arms
2 Arms
>0.98
Radiated immunity
Fast transients
Line surge immunity
Conducted immunity
Power freq. mag. field
EN61000-4-3
EN61000-4-4
EN61000-4-5
EN61000-4-6
EN61000-4-8
10,000 ft max.
30,000 ft max.
0.03 g2/Hz
20 g peak
Level B
Class A
Clause 5b
Level 3
Level 3
Level 3
Level 3
Level 3
Level 3
3 A/m
Input surge current
Internal input fuses
264 Vrms (cold start)
Both AC lines
40 A max. Voltage dip immunity
6.3 A
EN61000-4-11
Perf Criteria A, A, B
<5% UT 10 ms,
70% UT 500 ms,
40% UT 100 ms
NOTES:
1. Derate 1mA per ºC above 50 ºC ambient temperature
2. Leakage currents see page 5.
Product # AQ0400IUxx
Phone 1-888-567-9596
www.SynQor.com
Doc.# 005-005052 Rev. C
08/24/15
Page 2