English
Language : 

MINT1500 Datasheet, PDF (3/7 Pages) SL Power Electronics – 500W Single Output
MINT1500
500W Single Output
Medical & ITE Series
Auxiliary Signals
Power Good:
Signal goes HIGH 100-250mS after main
output is in regulation, and goes LOW with
7ms warning time before loss of main output
due to loss of AC input (Output is measured
above 90% nominal voltage)
Inhibit: Logic High or Open = On
Low/ground
= Off
Low or Open = ON
PS Off: Logic High = OFF
EMI/EMC Compliance
Conducted Emissions
Radiated Emissions
Static Discharge Immunity
Radiated RF Immunity
EFT/Burst Immunity
Line Surge Immunity
Conducted RF Immunity
Power Frequency Magnetic Field Immunity
Voltage Dip Immunity
Line Harmonic Emissions
Flicker Test
DC OK:
During normal operation, this signal is logic
HIGH. Signal will go LOW for output less than
90% of nominal.
Current Sharing Active single wire, for up to 3 units in parallel
EN55011/22 Class B, FCC Part 15, Subpart B, Class B
EN55011/22 Class A; FCC Part 15, Subpart A, Class A
EN61000-4-2, Criteria A, 6kV Contact Discharge, 8kV air discharge
EN61000-4-3, 3V/m;10V/M Criteria A, B
EN61000-4-4, 2kV/5kHz
EN61000-4-5, 1kV differential, 2kV common-mode
EN61000-4-6, 3Vrms
EN61000-4-8, 3A/m
EN61000-4-11, 0% Vin, 10mS; 40% Vin, 100mS (60% load); 70% Vin,
500mS (80% load); 0% 5000mS; Criteria A, A, A, B.
EN61000-3-2, Class A, and D
Meets Class C for 500 Watt output
EN61000-3-3, Complies
Isolation Specifications
Parameter
Insulation Safety Rating
Electric Strength Test Voltage
Conditions/Description
Input/Ground
Input/Output
Output/Ground
Input/Ground
Input/Output
Output/Ground
Min
1800
4000
700
Nom
1 MOPP
2 MOPP
Operational
Max
-
-
Units
Vac
Vac
Vdc
www.slpower.com
MINT1500 REV 6.0, 12-18-14
3