English
Language : 

MINT1400A_13 Datasheet, PDF (2/3 Pages) SL Power Electronics – 400W Single Output Series
MINT1400A
400W Single Output Series
Medical – Universal Input Power Supply
2 Year Warranty
Model
Number
MINT1400A1210L01
MINT1400A2410L01
MINT1400A2810L01
MINT1400A4810L01
Output
Volts (V)
12V
24V
28V
48V
Output Parameters
Output Current
Fan Cooled
Convection
33.0A
16.7A
14.3A
8.30A
21.0A
10.4A
8.9A
5.2A
Ripple
& Noise
1%
1%
1%
1%
Total
Regulation
2%
2%
2%
2%
Signals
Inhibit:
TTL LOW to inhibit
PS Off:
TTL HIGH to inhibit
Pwr OK
TTL HIGH when AC is OK, 100-200 mS delay.
Pwr OK
PF LOW 4 mS warning before loss of output regulation.
EMI/EMC Compliance
Conducted Emissions
Radiated Emissions
Voltage Fluctuations
Static Discharge Immunity
Radiated RF Immunity
EFT/Burst Immunity
Line Surge Immunity
Conducted RF Immunity
Power Frequency Magnetic Field Immunity
Voltage Dip Immunity
Line Frequency Harmonics
Output Power Derating Curve
DC OK:
HIGH when output is >90% of nominal
Fan Output:
12Vdc @ 250 mA.
5V Standby Voltage:
Always on, up to 100mA.
EN55011/22 Class B
EN55011/22 Class A
EN61000-3-3, complies
EN61000-4-2, 6kV Contact Discharge, 8kV air discharge
EN61000-4-3, 3V/m.
EN61000-4-4, 2kV/5kHz..
EN61000-4-5, 1kV differential, 2kV common-mode
EN61000-4-6, 3Vrms
EN61000-4-8, 3A/m
EN61000-4-11 criteria A @ 250 Watts or less.
EN61000-3-2, Class A
MINT1400 Output Power Derating Chart
450
400
350
300
250
200
150
100
50
0
0
Fan Cooled
Convection
10 20 30 40 50 60 70
Ambient Temperature (deg C)
Note: For convection cooling, the
power supply is required to be
mounted on a heatsink or system
chassis with a minimum of 150 in² of
surface area.
______________________________________________________________________________________________________________________________ 2 of 3