General Specifications
AC Input 100-240Vac, ±10%, 47-63Hz, 1∅
Turn On Time Less than 1 sec @115Vac, full load
Input Current 115Vac: 1.5A, 230Vac: 0.75A
Hold-up Time 20mS min., at full Load, 100Vac input
Inrush Current 264Vac, cold start: will not exceed 40A
Overtemperature Will shutdown upon an overtemperature
Protection condition, auto-recovery.
Input Fuses
F1, F2: 2A, 250Vac fuses (line & neutral lines)
provided on all models
Overload Protection 130 to 180% of rating, Hiccup Mode
Earth Leakage Input-GND: <500μA@264Vac, 60Hz, NC
Current Output-GND: <4mA@264Vac, 60Hz, NC
Short Circuit
Protection
Hiccup Mode, auto recovery.
Efficiency >88%, typical
Output Power
60W continuous – See models chart for
specific voltage model ratings.
No Load Input <0.210W (meets DoE Efficiency Level VI
Power Requirements)
Ripple and Noise See models chart on pg 1.
Output Voltage See models chart on pg 1.
Transient
Response
500µs response time for return to within 0.5%
of final value for any 50% load step over the
range of 5% to 100% of rated load, ∆i/∆t<
0.2A/µs. Max. voltage deviation is +/-3.5%.
Regulation See models chart on pg 1.
Overvoltage 130 to 150% of output voltage (max. 60V on
Protection 48V model), hiccup mode
Isolation
Safety Standards
Operating
Temperature
Input-Output: 2 MOPP
Input-Ground: 1 MOPP
Output-Ground: 1 MOPP
EN/IEC/UL60601-1, 3rd edition and
EN/IEC/UL60601-1-11:2010 for Home
Healthcare
-20°C to +50°C. Derate above 40°C.
Start Up at -40°C, full load, (warmup period before
all parameters are within published specifications).
Temperature Derate output power above 40°C to TBD at
Derating 50°C
Storage Temperature -40°C to +85°C
Altitude
Operating: to 5000m.
Non-operating: -500 to 40,000 ft.
Drop Test
1.4m from table top to wooden platform, 4
faces.
Vibration
Operating: 0.003g/Hz, 1.5grms overall, 3
axes, 10 min/axis, 1-500Hz.
Non-Oper.: random waveform, 3 minutes per
axis, 3 axes and Sine waveform, Vib.
frequency/acceleration: 10-500Hz/1g, sweep
rate of 1 octave / minutes, Vibration time of 10
sweeps / axes, 3 axes
Dimensions
W: 2.67” x L: 4.25” x H: 1.29”
W: 67.9mm x L: 108mm x H: 32.7mm
Weight 400g
All specifications are typical at nominal input, full load, at 25°C ambient unless noted.
Relative Humidity 5% to 95%, non-condensing
Shock
Operating: Half-sine, 20gpk, 10mS, 3 axes,
6 shocks total
Non-Operating: Half-sine waveform, impact
acceleration of 100G, Pulse duration of 6
mS, Number of shocks: 3 for each of the
three axis
MTBF
E-Cap Life
>250,000 hours, full load, 110 & 220Vac
input, 25°C amb., per Telcordia 332 Issue 6.
>7 year life based on calculations at
115Vac/60Hz & 230Vac/50Hz, ambient 25°C
at 24 hrs per day, 365 days/year, 6 power up
cycles per day. (80% load on 5V, 12V model)
www.slpower.com
ME60 Rev 2.4 31-JAN-16