English
Language : 

GPC225 Datasheet, PDF (2/2 Pages) SL Power Electronics – 225 Watt Global Performance Switchers
GPC225 Commercial/GPM225 Medical 225 Watt Multiple Output
Commercial Medical
Model
Model
Output
Output
Minimum
Output
Output
Maximum (B) Maximum (C)
Peak
Noise P-P Total Regulation (A)
GPC225-5 GPM225-5
5V
0A
34 A
40 A
45 A
50 mV
2%
GPC225-12 GPM225-12
12 V
0A
15.8 A
19 A
20 A
120 mV
2%
GPC225-15 GPM225-15
15 V
0A
12.7 A
15 A
16 A
150 mV
2%
GPC225-24 GPM225-24
24 V
0A
8.3 A
9.4 A
10 A
240 mV
2%
GPC225-28 GPM225-28
28 V
0A
7.1 A
8A
8.5 A
280 mV
2%
A.Total regulation is defined as the maximum deviation from the nominal voltage for all steady-state conditions of initial voltage setting, input line voltage and output load.
B. Unrestricted natural convection cooling.
C. Requires 26cfm moving air.
GPC225/GPM225 MECHANICAL SPECIFICATIONS
Environmental
Specification
Temperature (A)
Humidity (A)
Shock (B)
Altitude
Vibration (C)
Operating
See individual specs
0 to 95% RH
20 gpk
-500 to 10,000 ft
1.5 grms, 0.003 g2/Hz
Non-operating
-40 to +85oC
0 to 95% RH
40 gpk
-500 to 40,000 ft
5 grms, 0.026 g2/Hz
A. Units should be allowed to warm up/operate under non-condensing conditions
before application of power.
B. Random vibration—10 to 2000Hz, 6dB/octave roll-off from 350 to 2000Hz, 3
orthogonal axes.Tested for 10 min./axis operating and 1 hr./axis non-operating.
C. Shock testing—half-sinusoidal, 10 ± 3 ms duration, ± direction, 3 orthogonal axes,
total 6 shocks.
Condor D.C. Power Supplies, Inc., 2311 Statham Parkway, Oxnard, CA 93033
800-235-5929 • 805-486-4565 • FAX 805-487-8911 • www.condorpower.com