English
Language : 

G2M65 Datasheet, PDF (2/2 Pages) SL Power Electronics – G2M65-X, where X is any number from 12 through 48, which represents the output voltage rating.
ISOLATION: The creepage distance between primary and secondary circuits is 8 mm minimum. The
required creepage and clearance distances from primary circuits to secondary circuits must be
maintained after installation to preserve the intended safety.
TEMPERATURES: The maximum operating temperatures of certain safety components, as defined in
the applicable safety standards, must not be exceeded after installation to preserve the intended safety.
The output power, ambient air temperature and the availability, amount, direction and/or restriction of
airflow influence the temperatures of these components.
OVERCURRENT PROTECTION: The internal fuse for circuit protection is located in the phase lead
only. If a fuse is added to the neutral side or external dual fuses are provided, the fuse ratings must not
exceed that specified for the internal fuse, must meet the requirements of EN 60601-1, and be acceptable
for the country in which the host equipment is to be installed.
WARNING! RISK OF FIRE! A blown internal fuse is an indication of catastrophic failure of circuit
component(s). Refer to fuse marking on the supply for rating. Repair must be performed by Condor
authorized personnel.
WARNING! SHOCK HAZARD! Dangerous voltages are present on some components, printed wiring
traces and heatsinks.
EXPLANATION OF SYMBOLS
Alternating Current
Direct Current
Attention, Consult
Accompanying Documents
Attention, Dangerous Voltages
J1 Pin
1
3
AC Input
Line
Neutral
J3 Pin
1
2
+ Sense
- Sense
J2 Pin
1
2
3
4
5
6
CONNECTIONS
DC Output
MATING CONNECTORS
Output (+)
Output (+)
Output (+)
Return
J1 Amp Housing 640250-3 Contact 770476-1
J2 Amp Housing 640250-6 Contact 770476-1
J3 Amp MTA-100 Receptacle
Return
Return
CAUTION: Do not exceed 5 A per pin on J2.
SL Power Electronics, Corp. Inc. will not be liable for the safety, reliability or performance of these power supplies if a) any changes, modifications or repairs are carried out by other
than authorized agents of SL Power Electronics Corp., or b) the installation of the supply is not in accordance with these installation instructions and the applicable UL, CSA, and
EN/IEC safety standards.
41-35405-0001 Rev. C 6/8/06