English
Language : 

GPM200 Datasheet, PDF (1/2 Pages) SL Power Electronics – Maximum Continuous Output Power at 50°C With external 26 cfm Airflow = 200 W
CONDOR DC POWER SUPPLIES INC.
2311 STATHAM PKWY
OXNARD, CA 93033 + 805-486-4565
GPM200 SERIES
INSTALLATION INSTRUCTIONS
RATINGS
Input: 100-240 VAC, 5.5 A, 50/60 Hz
Output: Maximum Continuous Output Power at 50°C With external 26 cfm Airflow = 200 W
Standard Models:
Model
Output #1 1 Isc Output #2 1 Isc Output #3 Isc Output #4 2 Isc
GPM200A +5V 26A5 25A +12V 8.0A 15A -12V 1.2A 2A 12V 4.0A
2A
GPM200B +5V 26A5 25A +12V 8.0A 15A -5V 1.2A 2A 12V 4.0A
2A
GPM200D +5V 26A5 25A +24V 5.0A 15A -12V 1.2A 2A 12V 4.0A
2A
GPM200E +5V 26A5 25A +24V 5.0A 15A -15V 1.2A 2A 15V 4.0A
2A
GPM200F +5V 26A5 25A +12V 8.0A 15A -12V 1.2A 2A 5V 4.0A
2A
Special Models: (Place Code Letters for desired outputs from Table below; example = GPM200-BAA)
GPM200-
( ___ )
( ___ )
( ___ )
Output #11 Output #2 1
Output #3
Output #4 2
+5V 26A5 B = +12V 8.0A A = -5V 1.2A Q = -5V 2.4A A = 5V 4.0A
(For all C = +15V 8.0A B = -12V 1.2A R = -12V 2.4A B = 12V 4.0A
models) D = +24V 5.0A C = -15V 1.2A S = -15V 2.4A C = 15V 4.0A
D = 24V 2.0A
Notes:
1. The combined loads of Outputs No. 1 and No. 2 must not exceed 32 A.
2. Isolated output which may be referenced as a positive or negative voltage.
3. Maximum Operating Relative Humidity 96%, no condensation.
4. Isc = Maximum output short circuit current.
5. Minimum load current = 4A.
SAFETY DECLARATION: Condor DC Power Supplies, Inc. declares under our sole
responsibility that all models listed above are in conformity with the applicable requirements
of EN60950 following the provisions of the Low Voltage Directive 73/23/EEC.
CERTIFICATION: All models are Certified to be in compliance with the applicable requirements of
UL 2601-1 1st Ed, CSA 22.2 No. 234 (Level 3) (with additional tests to C22.2 No 601.1-M90 per T.I.L.
CA-08), IEC 601-1 (1988), EN 60601-1: 1990 and VDE 0750 T1 12.91.
CLASSIFICATION:
(In accordance with sub-
clause 5 of IEC 601-1)
(5.1) Protection against electric shock = Class I
(5.2) Degree of protection against electric shock = Signal output or intermediate
(5.3) Protection against harmful ingress of water = Ordinary (no protection)
(5.5) Has not been evaluated for use in the presence of a flammable anaesthetic mixture with
air, oxygen, or nitrous oxide. This evaluation is made on the end equipment by the OEM.
(5.6) Mode of operation = Continuous
CAUTION: When performing Dielectric Strength Tests, catastrophic failure of the unit may result if a
Dielectric Strength test voltage greater than 1800 Vac is applied between primary and secondary circuits.
The components providing isolation from primary to secondary cannot be tested while installed in the
power supply without overstressing basic (primary to ground) insulation. All isolating components are
individually 100% tested at 4800 Vac prior to installation.
41-33222-0001 Rev. E 1/29/02
Page 1 of 2