|
AN892 Datasheet, PDF (12/16 Pages) Silicon Laboratories – DESIGN GUIDE FOR ISOLATED DC/DC USING THE | |||
|
◁ |
AN892
N ï» V-----O----U-V--T---I-N-+---D--V----f--D----1- ï» 5--5---ï´--+---0--0-.--2.--5-5-- ï» 4.4
Equation 38.
A 1:4 turns ratio was chosen.
The next parameter to choose is the primary inductance. Equation 16 gives the average magnetizing current.
ImAVE = NILOAD = 4ï¨0.4ï© = 1.6A
Equation 39.
Equation 15 shows that magnetizing current ripple is inversely proportional to primary inductance. There are
considerations for choosing the magnitude of the magnetizing current ripple. Choosing a very small primary
inductance leads to a large current ripple. Care must be taken not to approach the cycle-by-cycle current limit of
approximately 3A. For this design, peak current was chosen not to exceed 2.5A at specified maximum ILOAD. A
ripple current of 1.8A was targeted. Rearranging Equation 15,
Lm + Llkg = V-----I-N----ID--m---ï¨ï¬--1-R----Iâ-P----DP---L-ï©--E-T----s---w--- = 5-----ï´-----0---.--2---5----ï¨---01---..--78---5----ï©--4----x---1---0----â---6- = 2.08ïH
Equation 40.
The result of Equation 40 suggests the combination of magnetizing current and leakage inductance should be
2.08 ïH. Leakage inductance is unavoidable in transformer design and it should be minimized for the best energy
transfer in an asymmetric half bridge flyback converter. A transformer was designed with primary inductance of
2 ïH and leakage inductance ï£100 nH. Figure 8 shows the expected magnetizing current during the portion of the
cycle that S1 is closed and S2 is open.
Figure 8. Magnetizing Current
12
Rev. 0.1
|
▷ |