Technical data (continued)
Circuit breaker
Tripping characteristics
In < 3 A
[ min ] [ sec ]
10'000
60
30 2`000
20
1`000
10
500
5
200
Type p
Rated current
Ambient temp.
TA35
<3A (TC-1, TC-2)
+23 °C
100
1
50
20
10
5
2
1
0,5
0,3
0,2
0,1
1,05 1,35
2
3
Multiple of rated current
45
8 10
[ x In ]
Tripping characteristics
In > 3 ... 20 A
[ min ] [ sec ]
10'000
60
30 2`000
20
1`000
10
500
5
200
Type
TA35
Rated current > 3–20A (TC-1, TC-2)
Ambient temp. +23 °C
100
1
50
20
10
5
2
1
0,5
0,3
0,2
0,1
1,05 1,35
2
3
Multiple of rated current
45
8 10
[ x In ]
Power entry modules without line filter
Effect of ambient temperature
The unit is calibrated for an ambient temperature of +23 °C. To
determine the rated current for lower or higher ambient temperature,
use a correction factor from the table below.
* Ambient
temperature [°C]
–25
–20
0
+23
+40
+50
+60
Correction factor
0.79
0.81
0.90
1.00
1.03
1.04
1.06
Order code (Order example)
Type Order code TA35
6136 C F T W F 1 2 0 C 0
see table 1
Please note that Schurter will establish an
internal part number for logistics use in
addition to the order code. The format of
this internal part number is, for example:
6136.xxxx.xxxx
.0210
* Temperature must be measured at the rear of the breaker
next to the terminals after equipment operating tempera-
ture has been reached.
Example:
Rated current at +23 °C
Ambient temperature
Correction factor
Chosen rated current at +60 °C
ambient temperature:
10 A
+60 °C
1.06
10 A x 1.06 = 10.6 A
Wiring
1 wired
0 unwired
Terminals
1 Quick connect 6.3 x 0.8 mm
Mounting
2 Snap-in s = 1.5 mm
3 Snap-in s = 2.0 mm
4 Snap-in s = 2.5 mm
0 Protection class 1
Appliance Inlet