English
Language : 

MADM Datasheet, PDF (2/2 Pages) Schurter Inc. – Special Fuse, 14.3 x 51 mm, 500 VAC, 250 VDC
MADM
www.schurter.com/pg01_2
Variants
Rated Cur-
rent [A]
Rated Vol-
tage [VAC]
Rated Vol- Breaking
tage [VDC] Capacity
Voltage Drop
1.0 In typ.
[mV]
1
500
250 1)
110 l
1.6
500
250 1)
80 l
2.5
500
250 1)
70 l
5
500
250 1)
75 l
8
500
250 1)
70 l
12.5
500
250 1)
70 l
20
500
250 1)
75 l
1) 100 kA @ 500 VAC , p.f. ≥ 0.15 / 10 kA @ 50 VDC , L/R < 10 ms
Packaging Unit
Small Box Pack (10 pcs.)
Order Number
7020.9110
7020.9120
7020.9130
7020.9140
7020.9150
7020.9160
7020.9170
Time-Current-Curves
100000
10000
1000
100
10
1
0.1
0.01
0.001
1
Multiple of Rated Current In
12.5 A In max. 0.5 s
25.0 A In max. 0.04 s
50.0 A In max. 0.009 s
10
Non resettable fuses
TFheusspeescifications, descriptions and illustrations indicated in this document are based on

current information. All content is subject to modifications and amendments.