English
Language : 

T13-212 Datasheet, PDF (1/6 Pages) Schurter Inc. – Circuit Breaker for Equipment thermal, Threaded neck type, Reset type, Screw terminals
Thermal (T- and TA-Line)
www.schurter.com /PG17_20
Circuit Breaker for Equipment thermal, Threaded neck type, Reset type, Screw terminals
T13-212
Description
- Threaded neck type
- Thermal circuit breaker
- 1‑pole
- Reset type
- Wide current range
- High breaking capacity
- Bolts and nuts
Unique Selling Proposition
- Compact design
- Positively trip-free release
- Available with cover
- Different mounting possibilities
Standards
-  IEC 60934
-  UL 1077
-  CSA C22.2 No. 235
-  GB 17701
Applications
- Power supplies
- Uninterruptible power supply
- Power tools
- Household appliances
Weblinks
pdf-datasheet, html-datasheet, General Product Information, Approvals,
CE declaration of conformity, RoHS, CHINA-RoHS, REACH, Distributor-
Stock-Check, Detailed request for product, Product News
Technical Data
Rated Voltage AC
Rated Voltage DC
Rated current range AC
Conditional short circuit ca-
pacity
Short circuit capacity Icn
␣
␣
Degree of Protection
Dielectric Strength
Insulation resistance
Endurance typical
Endurance minimum
240/277 V; 50/60 Hz, see approbations
28 V
0.05 - 30 A
IEC: Inc, PC1, AC 240 V: 1 kA
at In < 7 A/240 VAC : 8 x In
at In ≥ 7 A/240 VAC : 400 A
AC/DC 28 V : 400 A
from front side IP 40 acc. to IEC 60529
50 Hz: 1.5 kV
Impulse 1.2/50 μs: > 2.5 kV
500 VDC > 100 MΩ
2 x Ir: 3000 switching cycles
Reset type
AC : 2 x Ir , cos φ 0.6 :
DC : 2 x Ir , L/R = 2 - 3 ms :
50 switching cycles
Overload
␣
Ambient temperature
Vibration Resistance
Shock Resistance
Tripping Type
Actuation type
Weight
IEC: min. 40 trips
@ 6 x Ir, cos φ 0.6
UL / CSA: min. 50 trips
@ 1.5 x Ir, cos φ 0.75
-5 °C to 60 °C
± 1.5 mm @ 10 - 60 Hz
acc. to IEC 60068-2-6, test Fc
10 G @ 60 - 500 Hz
acc. to IEC 60068-2-6, test Fc
100 G / 6 ms
acc. to IEC 60068-2-27, test Ea
Thermal
Reset type
ca. 10 g
Circuit Breakers
1