T11-211 Datasheet, PDF (1/6 Pages) Schurter Inc. – Circuit Breaker for Equipment thermal, Threaded neck type, Reset type, Quick connect terminals | |||
|
Thermal (T- and TA-Line)
www.schurter.com /PG17_20
Circuit Breaker for Equipment thermal, Threaded neck type, Reset type, Quick connect terminals
T11-211
Description
- Threaded neck type 6 mm
- Thermal circuit breaker
- 1âpole
- Reset type
- Quick connect terminals 6.3 x 0.8 mm
Unique Selling Proposition
- Compact design
- Positively trip-free release
- Available with cover
- Different mounting possibilities
Standards
- Â IEC 60934
- Â UL 1077
- Â CSA C22.2 No. 235
- Â GB 17701
Technical Data
Rated Voltage AC
Rated Voltage DC
Rated current range AC
Conditional short circuit ca-
pacity
Short circuit capacity Icn
â£
Degree of Protection
Dielectric Strength
Insulation resistance
Endurance typical
Endurance minimum
240 V; 50/60 Hz
48 V
0.05 - 16 A
IEC: Inc, PC1, AC 240 V: 2 kA
at In < 6.5 A/240 VAC : 8 x In
at In ⥠6.5 A/240 VAC : 96 A
from front side IP 40 acc. to IEC 60529
50âHz: > 1.5âkV
Impulse 1.2/50 μs: > 2.5âkV
500âVDC > 100 MΩ
2 x Ir: 500âswitching cycles
Reset type
AC : 2 x Ir , cos Ï 0.6 :
DC : 2 x Ir , L/R = 2 - 3 ms :
50âswitching cycles
Applications
- Power tools
- Household Equipment
- Power supplies and chargers
- Industrial appliances
Weblinks
pdf-datasheet, html-datasheet, General Product Information, Approvals,
CE declaration of conformity, RoHS, CHINA-RoHS, REACH, Distributor-
Stock-Check, Detailed request for product, Product News
Overload
â£
Ambient temperature
Vibration Resistance
Shock Resistance
Tripping Type
Actuation type
Weight
IEC: min. 40âtrips
@ 6 x Ir, cos Ï 0.6
UL / CSA: min. 50âtrips
@ 1.5 x Ir, cos Ï 0.75
-5â°C to 60â°C
± 1.5 mm @ 10 - 60 Hz
acc. to IEC 60068-2-6, test Fc
5 G @ 60 - 500 Hz
acc. to IEC 60068-2-6, test Fc
100 G / 6âms
acc. to IEC 60068-2-27, test Ea
Thermal
Reset type
ca. 10âg
Circuit Breakers