English
Language : 

MAT Datasheet, PDF (1/3 Pages) Schurter Inc. – Special Fuse, 14 x 50 mm
MAT
Special Fuse, 14 x 50 mm
NON RESETTABLE FUSES
DTCN · 500 VAC · 250 VDC · Time-Lag T
Description
- High Breaking Capacity
Standards
- DTCN: T/5920 CC
Technical Data
Rated Voltage
Rated Current
Breaking Capacity
Characteristic
Admissible Ambient Air Temp.
Climatic Category
Material: Tube
Unit Weight
Storage Conditions
Product Marking
500 VAC, 250 VDC
1 - 20 A
100 kA
Time-Lag T
-40 °C to 55 °C
40/055/21 acc. to IEC 60068-1
Ceramic
25 g
0 °C to 60 °C, max. 70% r.h.
Voltage Rating
Dimensions
Length
References
General Product Information
Time-Current Curves see last page
Weblinks
Approvals: http://www.schurter.com/approvals
RoHS: http://www.schurter.com/rohs
50 mm
13
13 3
50+1.5
Pre-Arcing Time
Rated Current In
1 A - 20 A
1.25 x In
min.
60 min
1.65 x In
max.
60 min
2.0 x In
min.
2.5 s
5.0 x In
min.
30 ms
5.0 x In
max.
2.5 s
10.0 x In
min.
8 ms
10.0 x In
max.
200 ms
1 www.schurter.com