KP01145201 Datasheet, PDF (1/4 Pages) Schurter Inc. – IEC Appliance Inlet C14 with Fuseholder 1- or 2-pole | |||
|
Power entry modules without line filter
IEC Appliance Inlet C14 with Fuseholder 1- or 2-pole
KP (FH)
www.schurter.com/pg05
Medical fuse drawer
Inlet with fuseholder (5x20 mm)
C14
KPF Filter Module
(not enclosed)
70° C
Description
- Panel Mount:
Sandwich/rear-side
- 2 Functions:
Appliance Inlet Protection class I, Fuseholder for fuse-links 5 x 20 mm
1â or 2âpole
- For PCB mounting
- Alternative: version with line filter  KPF;  KPS
Approvals
- VDE License Number: 40008635
- UL License Number: E93617
- CSA License Number: 38456
Characteristics
- Panel mount from rear or "sandwich" between top and bottom/side to
side panels
PCB mount with snap-in or screw-on <BREAK/> feet (self tapping
screws à 3 x 8 mm)
- All single elements are already wired
- Fuse drawer meets requirements of medical standard IEC/EN 60601-1
The fuse drawer can only be opened with the aid of a tool
The fuseholder is accessible from the equipment front
- Insulation cover on the rear-side
- Qualified for use in equipment according IEC/EN 60950
Other versions on request
- Solder terminals
- Quick-connect terminals
- For protection class II
References
General Product Information
Weblinks
Approvals, RoHS, CHINA-RoHS, Mating Connectors, e-Store,
Distributor-Stock-Check, Accessories
Technical Data
Ratings IEC
Ratings UL/CSA
Dielectric Strength
Allowable Operation Temp.
Degree of Protection
Protection Class
Terminal
Panel Thickness s
Material: Housing
10âA / 250âVAC; 50âHz
10âA / 125âVAC; 60âHz
> 2.3âkVAC between L-N
> 2.8âkVAC between L/N-PE
(1âmin/50âHz)
-25â°C to 70â°C
from front side IP 40 acc. to IEC 60529
Suitable for appliances with protection
class 1 acc. to IEC 61140
For PCB mounting Quick connect termi-
nals 4.8 x 0.8 mm
Solder terminal on request
Snap-in: 1.5/2/2.5/3 mm
Thermoplastic, black, UL 94V-0
Appliance Inlet
Fuseholder
Rated Power Acceptance @
Ta 23 °C
Power Acceptance @ Ta >
23°C
C14 acc. to IEC/EN 60320-1,
UL 498, CSA C22.2 no. 42 (for cold
conditions) pin-temperature 70 °C, 10âA,
Protection Class 1
1 or 2 pole, Shocksafe category PC2
acc. to IEC 60127-6,
for fuse-links 5 x 20âmm
5 x 20: 2âW (1 pole)/ 1.6âW (2-pole) per
pole
Admissible power acceptance at hig-
her ambient temperature see derating
curves
Connectors
|
▷ |