English
Language : 

KMF Datasheet, PDF (1/6 Pages) Schurter Inc. – IEC Appliance Inlet with Filter, Fuseholder 1- or 2-pole, Line Switch 2-pole
Power Entry Modules with Line Filter
www.schurter.com/PG06
IEC Appliance Inlet with Filter, Fuseholder 1- or 2-pole, Line Switch 2-pole
KMF
Plug removal necessary for fuse
replacement
Protection class I with shield
Protection class II without shield
Order required accessories separately
C14
C18
70° C
70° C
Description
- Panel Mount:
Snap-in version from front side
- 4 Functions:
Appliance Inlet protection class I or II, Line Switch 2-pole, Fuseholder
for fuse-links 5 x 20 mm 1‑ or 2‑pole, Line filter in standard and medi-
cal version
- Quick connect terminals 4.8 x 0.8 mm
Unique Selling Proposition
- Most compact solution on the market
- Innovative EMC-shielding
- Easy and flexible snap-in mounting
- Protection class I or II versions
Approvals
- VDE Certificate Number: 40035743
- UL File Number: E72928
- CCC File Number: 2009010204326571
Technical Data
Ratings IEC
Ratings UL/CSA
Leakage Current
Dielectric Strength
Allowable Operation Temp.
Climatic Category
Degree of Protection
Protection Class
Terminal
Panel Thickness s
Material: Housing
1 - 10 A @ Ta 40 °C / 250 VAC; 50 Hz
1 - 10 A @ Ta 40 °C / 125 VAC; 60 Hz
standard < 0.5 mA (250 V / 60 Hz)
medical < 5 µA (250 V / 60 Hz)
> 1.7 kVDC between L-N
> 2.7 kVDC between L/N-PE
Test voltage (2 sec)
-25 °C to 85 °C
25/085/21 acc. to IEC 60068-1
from front side IP 40 acc. to IEC 60529
Suitable for appliances with protection
class I or II acc. to IEC 61140
Quick connect terminals 4.8 x 0.8 mm
Snap-in: 1/1.5/2/2.5 mm
(all steps with one variant)
Thermoplastic, black, UL 94V-0
Characteristics
- Ultra-compact design. Small dimensions in front of and behind the pa-
nel
- All single elements are already wired
- For added safety "Extra-Safe" fuse drawers are available
- Innovative EMC-shielding with flexible steel segments for an excellent
contact
- Suitable for use in equipment according to IEC/UL 60950
Suitable for use in medical equipment according to IEC/UL 60601-1
Other versions on request
- Fuse drawer 1-pole, plus spare fuse case
- Fuse drawer 2-pole, with shorting bar
- Other rocker marking
References
Alternative: version without line filter   KM
Alternative: version for screw mounting   DD12
Weblinks
pdf-datasheet, html-datasheet, General Product Information, Approvals,
CE declaration of conformity, RoHS, CHINA-RoHS, REACH, Mating
Connectors, e-Shop, SCHURTER-Stock-Check, Distributor-Stock-
Check, CAD-Drawings, Accessories, Wire Harnessing, Detailed request
for product
Appliance-Inlet/-Outlet
Fuseholder
Rated Power Acceptance @
Ta 23 °C
Power Acceptance @ Ta >
23°C
Line Switch
Line Filter
MTBF
C14 C18 acc. to IEC 60320-1,
UL 498, CSA C22.2 no. 42 (for cold
conditions) pin-temperature 70 °C, 10 A,
Protection Class I or II
1 or 2 pole, Shocksafe category PC2
acc. to IEC 60127-6,
for fuse-links 5 x 20 mm
5 x 20: 2 W (1 pole)/ 1.4 W (2-pole) per
pole
Admissible power acceptance at higher
ambient temperature see derating cur-
ves
2-pole, non-illuminated, acc. to IEC
61058-1
Technical Details
Standard and Medical Version, IEC
60939, UL 1283, CSA C22.2 no. 8
Technical Details
> 1'800'000 h acc. to MIL-HB-217 F
EMC Products
1