English
Language : 

EF12 Datasheet, PDF (1/6 Pages) Schurter Inc. – IEC Appliance Inlet C20 with Filter, Circuit Breaker TA45 (recessed)
Power Entry Modules with Line Filter
IEC Appliance Inlet C20 with Filter, Circuit Breaker TA45 (recessed)
www.schurter.com/pg06
EF12
Standard- or Medical-Filter
C20
70° C
Description
- Panel Mount:
Screw-on mounting from front side
- 3 Functions:
Appliance Inlet Protection class I, circuit breaker type TA45 2-
pole, Line filter in standard and medical version
- Quick connect terminals 6.3 x 0.8 mm
- Alternative: version without line filter  EF11
Approvals
- VDE License Number: 40001520
- UL License Number: E72928
Technical Data
Ratings IEC
Ratings UL/CSA
Leakage Current
Dielectric Strength
Allowable Operation Temp.
Climatic Category
Degree of Protection
Protection Class
Terminal
Panel Thickness s
Material: Housing
12 - 16 A @ Ta 40 °C / 250 VAC; 50 Hz
12 - 20 A @ Ta 40 °C / 125 VAC; 60 Hz
standard < 0.5 mA (250 V / 60 Hz)
medical < 5 µA (250 V / 60 Hz)
> 1.7 kVDC between L-N
> 2.7 kVDC between L/N-PE
Test voltage (2 sec)
-10 °C to 55 °C
10/055/21 acc. to IEC 60068-1
from front side IP 40 acc. to IEC 60529
Suitable for appliances with protection
class 1 acc. to IEC 61140
Quick connect terminals 6.3 x 0.8 mm
Screw: max 8 mm
Mounting screw torque max 0.5 Nm
Thermoplastic, black, UL 94V-0
Characteristics
- All single elements are already wired
- Line switch non-illuminated
Illuminated version on request
Thermal overload protection
Optional with undervoltage- or remote trip release
- With EMC-shield
- Qualified for use in equipment according IEC/EN 60950
References
General Product Information
Weblinks
Approvals, RoHS, CHINA-RoHS, Mating Connectors, e-Store,
Distributor-Stock-Check, Accessories
Appliance-Inlet/-Outlet
Circuit Breakers
Line Switch
Line Filter
MTBF
C20 acc. to IEC/EN 60320-1,
UL 498, CSA C22.2 no. 42 (for cold
conditions) pin-temperature 70 °C, 16 A,
Protection Class 1
Acc. IEC/EN 60934, UL 1077, CSA
22.2 no. 235
2-pole rocker switch, illuminated or non-
illuminated. Optional with undervoltage-
or remote trip release
Short circuit capacity Icn:
at In < 3A/240VAC : 10 x In
at In ≥ 3A/240VAC : 300A
Rocker switch 2-pole, non-illuminated
or illuminated, acc. to IEC 61058-1
Technical details
Standard and Medical Version, IEC
60939, IEC 60601‑1, UL 1283, UL 544,
EN 133 200, CSA C22.2 no. 8
Technical details
> 100'000 h acc. to MIL-HB-217 F
EMC Products