English
Language : 

DD22 Datasheet, PDF (1/5 Pages) Schurter Inc. – IEC Appliance Inlet C14 with Filter, Fuseholder 1- or 2-pole, Line Switch 2-pole, for PCB Mounting
Power Entry Modules with Line Filter
www.schurter.com/pg06
DD22
IEC Appliance Inlet C14 with Filter, Fuseholder 1- or 2-pole, Line Switch 2-pole, for PCB Mounting
Standard- or Medical-Filter
Fuse drawer must be ordered separately (see
accessories).
C14
70° C
Description
- Panel Mount:
Screw-on mounting on PCB, from rear-side
- 4 Functions:
Appliance Inlet Protection class I, Line Switch 2-pole, Fuseholder for
fuse-links 5 x 20 mm 1‑ or 2‑pole, Line filter in standard and medical
version
- PCB solder terminals
- Alternative: version without line filter  DD21
Approvals
- VDE License Number: 40001522
- UL License Number: E72928
Characteristics
- Ultra-compact design. Ideal for low profile designs
- All single elements are already wired
- For added safety "Extra-Safe" fuse drawers are available
Fuse drawer meets requirements of medical standard IEC/EN 60601-1
The fuse drawer can only be opened with the aid of a tool
The fuseholder is accessible from the equipment front
- Ideal for application with high transient loads
- Qualified for use in equipment according IEC/EN 60950
Other versions on request
- Fuse drawer 1-pole, plus spare fuse case
- Fuse drawer 2-pole, with shorting bar
- Other rocker marking
- Line switch, illuminated
- Line switch 1-pole
- Medical version M80
- Protection class II, 70°C
References
General Product Information
Weblinks
Approvals, RoHS, CHINA-RoHS, Mating Connectors, e-Store,
Distributor-Stock-Check, Accessories
Technical Data
Ratings IEC
Ratings UL/CSA
Leakage Current
Dielectric Strength
Allowable Operation Temp.
Climatic Category
Degree of Protection
Protection Class
Terminal
Panel Thickness s
Material: Housing
1 - 10 A @ Ta 40 °C / 250 VAC; 50 Hz
1 - 10 A @ Ta 40 °C / 250 VAC; 50/60 Hz
standard < 0.5 mA (250 V / 60 Hz)
medical < 5 µA (250 V / 60 Hz)
> 1.7 kVDC between L-N
> 2.7 kVDC between L/N-PE
Test voltage (1 min/50 Hz)
-25 °C to 85 °C
25/085/21 acc. to IEC 60068-1
from front side IP 40 acc. to IEC 60529
Suitable for appliances with protection
class 1 acc. to IEC 61140
For PCB mounting 3  mm additional
quick connect 6.3 x 0.8 mm
Screw-on mounting: max 3 mm
Mounting screw torque max 0.5 Nm
Thermoplastic, black, UL 94V-0
Appliance-Inlet/-Outlet
Fuseholder
Rated Power Acceptance @
Ta 23 °C
Power Acceptance @ Ta >
23°C
Line Switch
Line Filter
MTBF
C14 acc. to IEC/EN 60320-1
UL 498 CSA C22.2 no. 42 (for cold
conditions) pin-temperature 70 °C, 10 A,
Protection Class 1
1 or 2 pole, Shocksafe category PC2
acc. to IEC 60127-6,
for fuse-links 5 x 20 mm
5 x 20: 2 W (1 pole)/ 1.6 W (2-pole) per
pole
Admissible power acceptance at hig-
her ambient temperature see derating
curves
Rocker switch 2-pole, non-illuminated,
acc. to IEC 61058-1
Technical details
Standard and Medical Version, IEC
60939, IEC 60601‑1, UL 1283, UL 544,
EN 133 200, CSA C22.2 no. 8
Technical details
> 2'000'000 h acc. to MIL-HB-217 F
EMC Products