DD11 Datasheet, PDF (1/3 Pages) Schurter Inc. – IEC Appliance Inlet C14 with Line Switch 2-pole, Fuseholder 1- or 2-pole | |||
|
Power entry modules without line filter
IEC Appliance Inlet C14 with Line Switch 2-pole, Fuseholder 1- or 2-pole
www.schurter.com/pg05
DD11
Standard or Medical Fuse drawer
C14
70° C
Description
- Panel Mount:
Screw-on version from front or rear side
- 3 Functions:
Appliance Inlet Protection class I, Line Switch 2-pole, Fuseholder for
fuse-links 5 x 20 mm 1â or 2âpole
- Quick connect terminals 4.8 x 0.8 mm
- Alternative: version with line filter  DD12Â
- Alternative: version for snap-in mounting  KMÂ
- Alternative: version for PCB mounting  DD21
Approvals
- VDE License Number: 40018283
- UL License Number: E93617
Technical Data
Ratings IEC
Ratings UL/CSA
Dielectric Strength
Allowable Operation Temp.
Degree of Protection
Protection Class
Terminal
Panel Thickness s
Material: Housing
10âA / 250âVAC; 50âHz
8âA / 250âVAC; 60âHz ¹â¾
> 2.5âkVAC between L-N
> 3âkVAC between L/N-PE
(1âmin/50âHz)
-25â°C to 85â°C
from front side IP 40 acc. to IEC 60529
Suitable for appliances with protection
class 1 acc. to IEC 61140
Quick connect terminals 4.8 x 0.8 mm
Screw-on mounting: max 8âmm
Mounting screw torque max 0.5âNm
Rear side mounting: max 2 mm
Thermoplastic, black, UL 94V-0
1) with cover 7 A, without cover 8 A
Characteristics
- Ultra-compact design. Ideal for low profile designs
- All single elements are already wired
- Fuse drawer meets requirements of medical standard IEC/EN 60601-1
The fuseholder is accessible from the equipment front
For added safety "Extra-Safe" fuse drawers are available
- Ideal for application with high transient loads
Designed for standard and medical applications
- Qualified for use in equipment according IEC/EN 60950
Other versions on request
- Solder terminals
- Fuse drawer 1-pole, plus spare fuse case
- Fuse drawer 2-pole, with shorting bar
- Other rocker marking
- Line switch 1-pole
- Protection class II, 70°C
References
General Product Information
Weblinks
Approvals, RoHS, CHINA-RoHS, Mating Connectors, e-Store,
Distributor-Stock-Check, Accessories
Appliance Inlet
Fuseholder
Rated Power Acceptance @
Ta 23 °C
Power Acceptance @ Ta >
23°C
Line Switch
C14 acc. to IEC/EN 60320-1
UL 498, CSA C22.2 no. 42 (for cold
conditions) pin-temperature 70 °C, 10âA,
Protection Class 1
1 or 2 pole, Shocksafe category PC2
acc. to IEC 60127-6,
for fuse-links 5 x 20âmm
5 x 20: 2âW (1 pole)/ 1.6âW (2-pole) per
pole
Admissible power acceptance at hig-
her ambient temperature see derating
curves
Rocker switch 2-pole, non-illuminated
or illuminated, acc. to IEC 61058-1
Technical details
Connectors
|
▷ |