Power Entry Modules with Line Filter
IEC Appliance Inlet C14 with Filter, Fuseholder 1- or 2-pole, for PCB Mounting
www.schurter.com/pg06
DA22
Standard- or Medical-Filter and
-Fuse drawer
C14
70° C
Description
- Panel Mount:
Screw-on mounting on PCB, from rear-side
- 3 Functions:
Appliance Inlet, Fuseholder for fuse-links 5 x 20 mm, Line filter in stan-
dard and medical version
- PCB solder terminals
- Alternative: version for panel mounting  KFA
Approvals
- VDE License Number: 40001522
- UL License Number: E72928
Characteristics
- Ultra-compact design
- All single elements are already wired
- For added safety "Extra-Safe" fuse drawers are available
Fuse drawer meets requirements of medical standard IEC/EN 60601-1
The fuseholder is accessible from the equipment front
- Qualified for use in equipment according IEC/EN 60950
Other versions on request
- Fixing on PCB with self-tapping screws 3 mm or pre-inserted nuts M3
- Fuse drawer 1-pole, plus spare fuse case
- Fuse drawer 2-pole, with shorting bar
- Medical version M80, 220 nF X capacitors
- Class X1- and Y1-capacitors for enhanced withstand voltage
- Protection class II, 70°C
References
General Product Information
Weblinks
Approvals, RoHS, CHINA-RoHS, Mating Connectors, e-Store,
Distributor-Stock-Check, Accessories
Technical Data
Ratings IEC
Ratings UL/CSA
Leakage Current
Dielectric Strength
Allowable Operation Temp.
Climatic Category
Degree of Protection
Protection Class
Terminal
Panel Thickness s
Material: Housing
1 - 10 A @ Ta 40 °C / 250 VAC; 50 Hz
1 - 10 A @ Ta 40 °C / 125/250 VAC;
50/60 Hz ¹⁾
standard < 0.5 mA (250 V / 60 Hz)
medical < 5 µA (250 V / 60 Hz)
> 1.7 kVDC between L-N
> 2.7 kVDC between L/N-PE
Test voltage (1 min/50 Hz)
-25 °C to 85 °C
25/085/21 acc. to IEC 60068-1
from front side IP 40 acc. to IEC 60529
Suitable for appliances with protection
class 1 acc. to IEC 61140
For PCB mounting ; Additional for
ground terminal: Quick connect termi-
nals 6.3 x 0.8 mm angled to pin axis
Screw-on mounting: max 3 mm
Mounting screw torque max 0.5 Nm
Thermoplastic, black, UL 94V-0
1) UL appovals: 1-pole versions up to 10 A, 2-pole versions up to 8 A
Appliance-Inlet/-Outlet
Fuseholder
Rated Power Acceptance @
Ta 23 °C
Power Acceptance @ Ta >
23°C
Line Filter
MTBF
C14 acc. to IEC/EN 60320-1
UL 498 CSA C22.2 no. 42 (for cold
conditions) pin-temperature 70 °C, 10 A,
Protection Class 1
1 or 2 pole, Shocksafe category PC2
acc. to IEC 60127-6,
for fuse-links 5 x 20 mm
5 x 20: 2 W (1 pole)/ 1.4 W (2-pole) per
pole
Admissible power acceptance at hig-
her ambient temperature see derating
curves
Standard and Medical Version, IEC
60939, IEC 60601‑1, UL 1283, UL 544,
EN 133 200, CSA C22.2 no. 8