English
Language : 

AS168XDC2 Datasheet, PDF (1/6 Pages) Schurter Inc. – Circuit Breaker for Equipment thermal-magnetic, 2 poles
Thermal-magnetic (TM and AS-line)
www.schurter.com /PG20
Circuit Breaker for Equipment thermal-magnetic, 2 poles
AS168XDC2
Description
- Thermal-magnetic circuit breaker
- High short circuit performance
- Availability of AC and DC in the same frame size
- DIN-Rail Mounting
Standards
- Approval Reference Type: AS168X
-  IEC 60934
-  UL 1077
-  CSA C22.2
Applications
- Industrial appliances
Weblinks
pdf-datasheet, html-datasheet, General Product Information, Approvals,
CE declaration of conformity, RoHS, CHINA-RoHS, REACH, Distributor-
Stock-Check, Detailed request for product, Product News
Technical Data
General data
Rated Voltage DC
IEC 240 V
UL/CSA 240/360 V
Rated current
0.5 - 50 A , see approbations
Conditional short circuit capa- Icn: DC 240 V: 4.5 kA (no fuse)
city IEC 60934
Conditional short circuit capa-
city UL 1077
Icn: DC 240 V; DF/DG: 0.5A-40A: 10 kA
(no fuse)
Icn: DC 240 V; DH: 0.5A-40A: 5 kA (no
fuse)
Icn: DC 360 V; 0.5A-50A: 2 kA (no fuse)
Degree of Protection
from front side IP 40 acc. to IEC 60529
Dielectric Strength
Vibration Resistance
50 Hz: > 2 kV
Impulse 1.2/50 μs
± 0.75 mm @ 5 - 60 Hz
acc. to IEC 60068-2-6, test Fc
10 G @ 60 - 500 Hz
acc. to IEC 60068-2-6, test Fc
Insulation Resistance
Shock Resistance
250/440 VAC > 5 MΩ
30 G / 18 ms
acc. to IEC 60068-2-27, test Ea
Ambient temperature
-10 °C to 55 °C
Weight
100 - 130 g
Tripping Type
Actuation type
Permissible wire cross section
Switched neutral
Rated Voltage
Rated current
Function
Add-on modules
Add-on modules
Positively trip free
Manual ON/OFF
1.5 - 25 mm² / 16 - 4 AWG
AC 277 V
AC/DC 65 A
The switched neutral closes with ma-
nual closure of the poles and opens
automatically with thermal magnetic
tripping of the poles.
Technical data for the additional module
see separate data sheet
Circuit Breakers
1