English
Language : 

AS168XAC4 Datasheet, PDF (1/7 Pages) Schurter Inc. – Manual Motor Controller / Circuit Breaker for Equipment thermal-magnetic, 4 poles
Thermal-magnetic (TM and AS-line)
www.schurter.com /PG20
Manual Motor Controller / Circuit Breaker for Equipment thermal-magnetic, 4 poles
AS168XAC4
Description
- Thermal-magnetic circuit breaker
- High short circuit performance
- Availability of AC and DC in the same frame size
- DIN-Rail Mounting
Standards
- Approval Reference Type: AS168X
-  IEC 60934
-  UL508, UL1077
-  CSA C22.2
Applications
- Industrial appliances
Weblinks
pdf-datasheet, html-datasheet, General Product Information, Approvals,
CE declaration of conformity, RoHS, CHINA-RoHS, REACH, Distributor-
Stock-Check, Detailed request for product, Product News
Technical Data
General data
Rated Voltage AC
IEC : 420 V Y / 240 V;  50/60 Hz
␣
UL/CSA : 480 V Y / 277 V;  50/60 Hz
Rated Voltage DC
65 V
Rated current
0.5 - 52 A , see approbations
Conditional short circuit capa- Icn: AC 420 V Y/240 V / DC 65 V: 5 kA
city IEC 60934
(no fuse)
Conditional short circuit capa-
city UL 1077
Inc: AC 480 V Y/277 V: 10 kA (with fuse
class H/J, 4x rated current (min. 15 A))
Icn: AC 480 V Y/277 V: 5 kA (no fuse)
Icn: DC 65 V: 2 kA (no fuse)
Conditional short circuit capa- Icn: AC 480 V Y/277 V: 5 kA (no fuse)
city UL 508
Degree of Protection
from front side IP 40 acc. to IEC 60529
Lifetime
1 x Ir 6000 switching cycles
Dielectric Strength
Vibration Resistance
50 Hz: > 2 kV
Impulse 1.2/50 μs
± 0.75 mm @ 5 - 60 Hz
acc. to IEC 60068-2-6, test Fc
10 G @ 60 - 500 Hz
acc. to IEC 60068-2-6, test Fc
Insulation Resistance
Shock Resistance
250/440 VAC > 5 MΩ
30 G / 18 ms
acc. to IEC 60068-2-27, test Ea
Ambient temperature
-10 °C to 55 °C
Weight
100 - 130 g
Tripping Type
Actuation type
Permissible wire cross section
Switched neutral
Rated Voltage
Rated current
Function
Add-on modules
Add-on modules
Positively trip free
Manual ON/OFF
1.5 - 25 mm² / 16 - 4 AWG
AC 277 V
AC/DC 65 A
The switched neutral closes with ma-
nual closure of the poles and opens
automatically with thermal magnetic
tripping of the poles.
Technical data for the additional module
see separate data sheet
Circuit Breakers
1