AS168XAC1 Datasheet, PDF (1/8 Pages) Schurter Inc. – Manual Motor Controller / Circuit Breaker for Equipment thermal-magnetic, 1 pole | |||
|
Thermal-magnetic (TM and AS-line)
www.schurter.com /PG20
Manual Motor Controller / Circuit Breaker for Equipment thermal-magnetic, 1 pole
AS168XAC1
Description
- Thermal-magnetic circuit breaker
- High short circuit performance
- Availability of AC and DC in the same frame size
- DIN-Rail Mounting
Standards
- Approval Reference Type: AS168X
- Â IEC 60934
- Â UL508, UL1077
- Â CSA C22.2
Technical Data
General data
Rated Voltage AC
IEC : 240 V;Â Â 50/60 Hz
â£
UL/CSA : 277 V;Â Â 50/60 Hz
Rated Voltage DC
65 V
Rated current
0.5 - 52 A , see approbations
Conditional short circuit capa- Icn: AC 240 V / DC 65 V: 5 kA (no fuse)
city IEC 60934
Conditional short circuit capa-
city UL 1077
Inc: AC 277 V: 10 kA (with fuse class
H/J, 4x rated current (min. 15 A))
Icn: AC 125 V: 10 kA (no fuse)
Icn: AC 277 V: 5 kA (no fuse)
Icn: DC 65 V: 2 kA (no fuse)
Conditional short circuit capa- Icn: AC 277 V: 5 kA (no fuse)
city UL 508
Degree of Protection
from front side IP 40 acc. to IEC 60529
Lifetime
1 x Ir : 6000âswitching cycles
Dielectric Strength
Vibration Resistance
50âHz: > 2âkV
Impulse 1.2/50 μs
± 0.75 mm @ 5 - 57 Hz
acc. to IEC 60068-2-6, test Fc
10 G @ 57 - 500 Hz
acc. to IEC 60068-2-6, test Fc
Insulation Resistance
Shock Resistance
250/440âVAC > 5 MΩ
25 G / 10âms
acc. to IEC 60068-2-27, test Ea
Ambient temperature
-20â°C to 60â°C
Weight
100 - 130âg
Applications
- Industrial appliances
Weblinks
pdf-datasheet, html-datasheet, General Product Information, Approvals,
CE declaration of conformity, RoHS, CHINA-RoHS, REACH, Distributor-
Stock-Check, Detailed request for product, Product News
Tripping Type
Actuation type
Permissible wire cross section
Switched neutral
Rated Voltage
Rated current
Function
Add-on modules
Add-on modules
Positively trip free
Manual ON/OFF
1.5 - 25 mm² / 16 - 4 AWG
AC 277 V
AC/DC 65 A
The switched neutral closes with ma-
nual closure of the poles and opens
automatically with thermal magnetic
tripping of the poles.
Technical data for the additional module
see separate data sheet
Circuit Breakers
1
|
▷ |