English
Language : 

5707 Datasheet, PDF (1/6 Pages) Schurter Inc. – IEC Appliance Inlet C14 or C18 with Filter, Protection Degree IP65, Fuseholder 1- or 2-pole, Front or Rear Mounting
Power Entry Modules with Line Filter
www.schurter.com/pg06
IEC Appliance Inlet C14 or C18 with Filter, Protection Degree IP65, Fuseholder 1- or 2-pole, Front or Rear
Mounting
5707
Medical fuse drawer
Mounting from front side
C14
C18
Mounting from rear side
70° C
70° C
Description
- Panel Mount:
Screw-on version from front or rear side, Screws with sealing are inclu-
ded
- 4 Functions:
Appliance Inlet protection class I or II, Line filter in standard and medi-
cal version, Fuseholder for fuse-links 5 x 20 mm, IP 65 protection
- Quick connect terminals 6.3 x 0.8 mm
Approvals
- VDE License Number: 40016382
- UL License Number: E72928
Characteristics
- Extreme robust design
- All single elements are already wired
- Screw type fuse carrier, slotted
Fuseholder meets requirements of medical standard IEC/EN 60601-1
The fuseholder can only be opened with the aid of a tool
The fuseholder is accessible from the equipment front
- With EMC-shield
- Especially for applications in rough environments
- Qualified for use in equipment according IEC/EN 60950
Other versions on request
- With solder terminals
- Class X1- and Y1-capacitors for enhanced withstand voltage
- Medical version M80
- Additional sealing (IP54) of power input
- Version with current rating 3 A
References
General Product Information
Weblinks
Approvals, RoHS, CHINA-RoHS, Mating Connectors, Distributor-Stock-
Check, Accessories
Technical Data
Ratings IEC
Ratings UL/CSA
Leakage Current
Dielectric Strength
Allowable Operation Temp.
Climatic Category
Degree of Protection
Protection Class
Terminal
Panel Thickness s
Material: Housing
1 - 8 A @ Ta 40 °C / 250 VAC; 50 Hz
1 - 8 A @ Ta 40 °C / 125 VAC; 60 Hz
standard < 0.5 mA (250 V / 60 Hz)
medical < 5 µA (250 V / 60 Hz)
> 1.7 kVDC between L-N
> 2.7 kVDC between L/N-PE
Test voltage (2 sec)
-25 °C to 85 °C
25/085/21 acc. to IEC 60068-1
from front side IP 65 acc. to IEC 60529
from rear-side IP 65 acc. to IEC 60529
Suitable for appliances with protection
class 1 or 2 acc. to IEC 61140
Quick connect terminals 6.3 x 0.8 mm
Screw, max 3 mm
Mounting screw torque max 0.8 Nm
2 screws M3 with sealing are provided
black / metallic, UL 94V-0
Appliance-Inlet/-Outlet
Fuseholder
Rated Power Acceptance @
Ta 23 °C
Power Acceptance @ Ta >
23°C
Line Filter
MTBF
C14 acc. to IEC/EN 60320-1
UL 498, CSA C22.2 no. 42 (for cold
conditions) pin-temperature 70 °C, 8 A,
Protection Class 1 or 2
1 or 2 pole, Shocksafe category PC2
acc. to IEC 60127-6,
for fuse-links 5 x 20 mm
5 x 20: 1.6 W 1-pole/ 1,2 W 2-pole per
pole
Admissible power acceptance at hig-
her ambient temperature see derating
curves
Standard and Medical Version, IEC
60939, IEC 60601‑1, UL 1283, UL 544,
EN 133 200, CSA C22.2 no. 8
Technical details
> 2'800'000 h acc. to MIL-HB-217 F
EMC Products