5220 Datasheet, PDF (1/5 Pages) Schurter Inc. – IEC Appliance Inlet C14 with Filter, Fuseholder 1- or 2-pole
Power Entry Modules with Line Filter
IEC Appliance Inlet C14 with Filter, Fuseholder 1- or 2-pole
www.schurter.com/pg06
5220
Plug removal necessary for fuse
replacement
Typ 5220, Fuseholder 2-pole
Snap-In Version or Screw-On Version
C14
Typ 5220, Fuseholder 2-pole
Snap-In Version or Screw-On Version
70° C
Description
- Panel Mount:
Snap-in or screw-on mounting from front side
- 3 Functions:
Appliance Inlet Protection class I, Fuseholder for fuse-links 5 x 20 mm
2-pole, Line filter in standard and medical version
- Quick connect terminals 6.3 x 0.8 mm
- Alternative: version without line filter  6220
Approvals
- VDE License Number: 101307
- UL License Number: E72928
- CSA License Number: 97784
Technical Data
Ratings IEC
Ratings UL/CSA
Leakage Current
Dielectric Strength
Allowable Operation Temp.
Climatic Category
Degree of Protection
Protection Class
Terminal
Panel Thickness s
Material: Housing
1 - 10 A @ Ta 40 °C / 250 VAC; 50 Hz
1 - 10 A @ Ta 40 °C / 125 VAC; 60 Hz
standard < 0.5 mA (250 V / 60 Hz)
medical < 5 µA (250 V / 60 Hz)
> 1.7 kVDC between L-N
> 2.7 kVDC between L/N-PE
Test voltage (2 sec)
-25 °C to 85 °C
25/085/21 acc. to IEC 60068-1
from front side IP 40 acc. to IEC 60529
Suitable for appliances with protection
class 1 acc. to IEC 61140
Quick connect terminals 6.3 x 0.8 mm
Screw: max 8 mm
Mounting screw torque max 0.5 Nm
Snap-in: 0.8 mm to 3 mm
Thermoplastic, black, UL 94V-0
Characteristics
- All single elements are already wired
- Plug removal necessary for fuse-link replacement
Fuse drawer meets requirements of medical standard IEC/EN 60601-1
The fuseholder is accessible from the equipment front
- Qualified for use in equipment according IEC/EN 60950
References
General Product Information
Weblinks
Approvals, RoHS, CHINA-RoHS, Mating Connectors, e-Store,
Distributor-Stock-Check, Accessories
Appliance-Inlet/-Outlet
Fuseholder
Rated Power Acceptance @
Ta 23 °C
Power Acceptance @ Ta >
23°C
Line Filter
MTBF
C14 acc. to IEC/EN 60320-1,
UL 498, CSA C22.2 no. 42 (for cold
conditions) pin-temperature 70 °C, 10 A,
Protection Class 1
2-pole, Shocksafe category PC2 acc. to
IEC 60127-6,
for fuse-links 5 x 20 mm
5 x 20: 1.6 W (2-pole)
Admissible power acceptance at hig-
her ambient temperature see derating
curves
Standard and Medical Version, IEC
60939, IEC 60601‑1, UL 1283, UL 544,
EN 133 200, CSA C22.2 no. 8
Technical details
> 2'300'000 h acc. to MIL-HB-217 F
EMC Products