English
Language : 

PM9105AP Datasheet, PDF (3/10 Pages) Sames – THREE PHASE POWER/ENERGY METERING MODULE
PM9105AP
ELECTRICAL CHARACTERISTICS
(Over the temperature range -10°C to +70°C, unless otherwise specified.
Parameter
Supply Voltage (x3 Phases)
(Continuous)
Frequency Output
Power Consumption1
Symbol Min Typ Max Unit Condition
VAC
180 230 265 V PM9105APE
FOUTX Refer to applicable IC data sheet
100 m W V = 5V
DD
Note 1: Power consumption specifications exclude power consumed by the current
sensors.
CONNECTION DESCRIPTION
Designation
PL5
Description
Voltage Supply connected to Phase 1
Voltage Supply connected to Phase 2
Voltage Supply connected to Phase 3
Voltage Supply connected to Neutral Line (Common)
PL6
Power Output: 4Hz at rated current
Power Output: 290 Hz at rated current
Power Output: 1160 Hz at rated current
0V (Common)
PL4
5V DC Supply Voltage
0V DC Supply Voltage
CT1
Phase 1 (Direction indicated on PCB)
CT2
Phase 2 (Direction indicated on PCB)
CT3
Phase 3 (Direction indicated on PCB)
FUNCTIONAL DESCRIPTION
1. Power Calculation
In the Application Circuit (see Figure 2), the output currents from the current sensors
will be between 0 and 16µA. The current input stages saturate at input currents
greater than 18µA . The mains voltage (mains voltage + 15% - 20%) is used for
RMS
the power calculation, together with the current information from the current sensors
(current transformers).
The calculated power for the 3 phases is integrated over time and converted into a
corresponding frequency.
sames
3/10