PU110_14 Datasheet, PDF (1/2 Pages) RSG Electronic Components GmbH – 72-110 WATT ITE POWER SUPPLIES
72-110 WATT ITE POWER SUPPLIES
DESCRIPTION
The PU110 series of compact, open PCB constructed,
AC-DC switching power supplies are capable of
delivering 72-110 watts of continuous power at 25 CFM
forced air cooling or 60-80 watts at convection cooling.
They operate at 85-264 VAC input voltage without the
need of a selector strap. They are ideally suited for use
in small to medium size digitally-based systems, such as
point-of-sale equipment, microprocessor based systems,
and telecom equipment. All models meet the safety
requirements of UL, CSA and IEC.
FEATURES
z Recognized or certified by UL, CSA and TÜV
z Power Fail Detect (PFD)signal
z 100% burn-in
z Wide input range 85-264 VAC
z Input surge current protection
z Overvoltage protection
z Overcurrent protection
z Compliant with RoHS requirements
INPUT SPECIFICATIONS
Input voltage:
85-264 VAC
Input frequency:
47-63Hz
Input current:
3.20 A (rms) for 115 VAC
1.80 A (rms) for 230 VAC
Earth leakage current:
0.40 mA max. @ 115 VAC, 60 Hz
(Touch current)
0.75 mA max. @ 230 VAC, 50 Hz
OUTPUT SPECIFICATIONS
Output voltage /current:
See rating chart.
Maximum output power:
See rating chart.
Ripple and noise:
Overvoltage protection:
Overcurrent protection:
Temperature coefficient:
1% peak to peak maximum
Provided on output #1 only; set at
112-132% of its nominal output
voltage
All outputs protected to short circuit
conditions
All outputs ±0.04% /℃ maximum
Transient response:
Maximum excursion of 4% or better on
all models, recovering to 1% of final
value within 500 us after a 25% step
load change
INTERFACE SIGNALS
PFD:
TTL logic high for normal operation and TTL logic low
upon loss of input power. This signal appears at least
1 ms prior to +5V output dropping 5% below its
nominal value. This signal also provides a minimum
delay of 100 ms after +5V is within regulation.
ENVIRONMENTAL SPECIFICATIONS
Operating temperature: 0℃ to +70℃
Storage temperature:
-40℃ to +85℃
Relative humidity:
5% to 95% non-condensing
Derating:
Derate from 100% at +50℃ linearly to
50% at +70℃
Cooling:
110 watts continuous output power at 25
CFM forced air cooling or 80 watts at
convection cooling
PU110 SERIES
(LVD)
RoHS
SAFETY STANDARD APPROVALS
UL 60950-1
File No. E137410
CSA C22.2 No. 60950-1
File No. LR93632
TÜV EN 60950-1
Certificate No. R9352008
GENERAL SPECIFICATIONS
Switching frequency:
Efficiency:
20 KHz to 250 KHz, varied with load and
line
70% minimum on single output models
with Vo ≧12V, 65% minimum on the
Hold-up time:
Line regulation:
Inrush current:
others
12 ms minimum at 110 VAC
±0.5% maximum at full load
15 A @ 115 VAC or 30 A @ 230VAC, at
25℃ cold start
Withstand voltage:
MTBF:
3000 VAC from input to output,
1500 VAC from input to ground,
500 VAC from output to ground
400,000 hours minimum at full load
at 25℃ ambient, calculated per
MIL-HDBK-217F
EMC Performance (EN55024)
EN55022:
Class B conducted, Class B radiated
FCC:
Class B conducted, Class B radiated
VCCI:
Class B conducted, Class B radiated
EN61000-3-2:
Harmonic distortion, Class A
EN61000-3-3:
Line flicker
EN61000-4-2:
ESD, ±8 KV air and ±4 KV contact
EN61000-4-3:
Radiated immunity, 3 V/m
EN61000-4-4:
Fast transient/burst, ±1 KV
EN61000-4-5:
Surge, ±1 KV diff., ±2 KV com.
EN61000-4-6:
Conducted immunity, 3 Vrms
EN61000-4-8:
Magnetic field immunity, 1 A/m
EN61000-4-11:
Voltage dip immunity, 30% reduction for
500 ms, and >95% reduction for 10 ms
OUTPUT POWER DERATING CURVE
59