KHEA120F-24 Datasheet, PDF (1/4 Pages) RSG Electronic Components GmbH – AC-DC Power Supplies DIN Rail type
AC-DC Power Supplies DIN Rail type
KHEA series
Ordering information
KHE A 240 F
1
2
3
4
-24 -O
5
6
Recommended EMI/EMC Filter
KHEA120F NAC-04-472
KHEA240F NAC-06-472
1Series name
2Single output
3Output wattage
4Universal input
5Output voltage
6Option
C : with Coating
N2: Screw mounting
High voltage pulse noise type : NAP series
Low leakage current type : NAM series
*The EMI/EMC Filter is recommended
to connect with several devices.
MODEL
MAX OUTPUT WATTAGE[W]
DC OUTPUT
KHEA120F-24
120
24V 5A (Peak 7.5A)
KHEA240F-24
240
24V 10A (Peak 15A)
KHEA480F-24 PRELIMINARY
480
24V 20A (Peak 30A)
SPECIFICATIONS
MODEL
KHEA120F-24
KHEA240F-24
KH
VOLTAGE[V]
AC85 - 264 1f or DC120 - 370
ACIN 115V 1.2typ
2.3typ
CURRENT[A]
ACIN 230V 0.6typ
1.2typ
KHEA480F-24
4.6typ
2.3typ
FREQUENCY[Hz]
50 / 60 (47 - 63) or DC
INPUT
EFFICIENCY[%]
ACIN 115V 90typ
ACIN 230V 92typ
92typ
94typ
92typ
94typ
POWER FACTOR
ACIN 115V
ACIN 230V
INRUSH CURRENT[A] ACIN 115V
*1 ACIN 230V
0.98typ
0.93typ
15typ (at cold start Ta=25C)
30typ (at cold start Ta=25C)
0.98typ
0.93typ
20typ (more than 3 sec. to re-start)
40typ (more than 3 sec. to re-start)
0.98typ
0.93typ
LEAKAGE CURRENT[mA] 0.45 / 0.75max (ACIN 100V / 240V 60Hz, Io=100%, According to IEC60950-1 and DEN-AN)
VOLTAGE[V]
24
24
24
CURRENT[A]
5
10
20
PEAK CURRENT[A]
*2 7.5
15
30
LINE REGULATION[mV] *3 96max
LOAD REGULATION[mV] *3,*4 150max
0 to +70C 120max
RIPPLE[mVp-p] *5 -25 - 0C 240max
OUTPUT
Io=0 - 30% 240max *4
0 to +70C 150max
RIPPLE NOISE[mVp-p] *5 -25 - 0C 300max
Io=0 - 30% 300max *4
TEMPERATURE REGULATION[mV] 0 to +70C 240max
*4 -25 to +70C 360max
DRIFT[mV]
*6 96max
START-UP TIME[ms]
750max (ACIN 115V, Io=100%)
HOLD-UP TIME[ms]
20typ (ACIN 115V, Io=100%)
OUTPUT VOLTAGE ADJUSTMENT RANGE[V]
OUTPUT VOLTAGE SETTING[V]
22.5 to 28.5
24.0±1.0%
OVERCURRENT PROTECTION Works over 101% of peak current and recovers automatically
PROTECTION OVERVOLTAGE PROTECTION[V] 30.0 to 36.0
CIRCUIT AND DC_OK LAMP
LED (Green)
OTHERS
ALARM LAMP
LED (Red)
ISOLATION
ENVIRONMENT
DC_OK CONTACT
INPUT-OUTPUT
INPUT-PE
OUTPUT-PE
OUTPUT-RC, DC_OK
OPERATING TEMP.,HUMID.AND ALTITUDE
STORAGE TEMP.,HUMID.AND ALTITUDE
VIBRATION
*9
Relay contact 30VDC 1A max, 30VAC 0.5A max (resistive load)
AC3,000V 1minute, Cutoff current = 10mA, DC500V 50MW minʢAt Room Temperatureʣ
AC2,000V 1minute, Cutoff current = 10mA, DC500V 50MW minʢAt Room Temperatureʣ
AC500V 1minute, Cutoff current = 100mA, DC500V 50MW minʢAt Room Temperatureʣ
AC500V 1minute, Cutoff current = 100mA, DC500V 50MW minʢAt Room Temperatureʣ
-25 to +70C (Required to Derating), 20 - 90%RH (Non condensing), 3,000m (10,000 feet) max
-40 to +85C, 20 - 90%RH (Non condensing)
10 - 55Hz, 19.6m/s2 (2G), 3minutes period, 60 minutes along Z axis (Non operating, mounted on DIN Rail)
IMPACT
196.1m/s2 (20G), 11ms, once each X, Y and Z axis (Packing state)
SAFETY AND AGENCY APPROVALS (At only AC input) UL60950-1, C-UL (CSA60950-1), EN60950-1, EN50178, UL508, ANSI / ISA12.12.01 Complies with DEN-AN
NOISE
CONDUCTED NOISE
Complies with FCC Part15 classB, VCCI-B, CISPR22-B, EN55011-B, EN55022-B
REGULATIONS
OTHERS
HARMONIC ATTENUATOR
CASE SIZE
*8
WEIGHT
Complies with IEC61000-3-2Ê¢Class A) *7
37X124X117mm (WXHXD)
50X124X117mm (WXHXD)
[1.46X4.88X4.61 inches]
[1.97X4.88X4.61 inches]
700g max
900g max
75X124X117mm (WXHXD)
[2.95X4.88X4.61 inches]
1,100g max
COOLING METHOD
Convection / Forced air
*1 The value is primary surge. The current of input surge to a built-in EMI/EMC Filter(0.2ms or less)is
excluded.
*2 Peak current for 5sec.And Duty 35% max.Refer to the instruction manual 3.
*3 Please contact us about dynamic load and input response.
*4 The output voltage is below 23.5V, the value is equal to three times of the specification.
*5 This is the value that measured on measuring board with capacitor of 22mF and 0.1mF at 150mm from
output terminal.
Measured by 20MHz oscilloscope or Ripple-Noise meter (Equivalent to KEISOKU-GIKEN: RM103).
Please refer to the instruction manual 2.7.
KH-2
*6 Drift is the change in DC output for an eight hour period after a half-hour warm-up at 25C, with the
input voltage held constant at the rated input/output.
*7 Please contact us about another class.
*8 Case size contains neither the umbo.
*9 Only as standard mounting orientation (A). Refer to 5.1.
If install other than standard mounting orientation (A), please fix the power supply for withstand the
vibration and impact.
* To meet the specifications. Do not operate over-loaded condition.
* A sound may occur from power supply at peak loading.