DPP15-100 Series
15-100W, 5-48V Output
DIN Rail Mount Power Supplies
DPP15-100 Features and Benefits
• Low Cost
• 5V to 48V Outputs
• Universal Input
• Compact Size
• NEC Class 2 Compliant
• UL508 Listed
• -10 to +71°C Operation
• RoHS Compliant
Key Market Segments & Applications
Industrial Controls:
Factory Automation:
Test & Measurement:
Motor Control Systems
Process Control, Automotive,
Chemical Processing
Burn in & Test,
Instrumentation Measurement
Features
• PFC Compliant to EN61000-3-2
• UL508 Approvals
• TS35/7.5 or TS35/15 DIN Rail Mounting
Specifications
Benefits
• Supports Global Use
• Easier System Configuration
• Easy System Integration
ITEMS
MODELS
DPP15
DPP25/30
DPP50
DPP100
AC Input Voltage range (1)
Input Frequency
DC Input Voltage range
Inrush Current (115 / 230VAC)
Power Factor
Max Input Current (230VAC)
Output Voltage Accuracy
Line Regulation
Load Regulation
Ripple/Noise
Overcurrent Protection (Typ)
Overvoltage Protection
Hold Up Time (115VAC input)
Parallel switch
LED Indicator
Operating Temperature
Storage Temperature
Operating Humidity
Cooling
(2)
Withstand Voltage
Shock
Vibration
Isolation Resistance
Safety Agency Approvals
Emissions
Immunity
Weight (Typ)
Size (WxHxD)
Case material
MTBF (MIL-HDBK-217F, GF25)
Warranty
VAC
Hz
-
A
-
A
%
%
%
mV
-
V
ms
-
-
-
-
-
-
-
-
-
-
-
-
-
g
mm
-
Hours
-
85 - 264VAC
85 - 132VAC
176 - 264VAC
47 - 63Hz
90 - 375VDC
210 - 375VDC
<35A
35 / 45A
35 / 50A
35 / 55A
Meets EN61000-3-2 Class A
0.4
0.72
1.35
2.2
±1% (24V outputs preset at 24.5V)
< 0.5%
< 0.5%
<50mV (20MHz Bandwith)
>120%
125 - 137.5%, Cycle AC line to reset
> 20ms
No
Yes
Green LED = On
-10 to +71°C (Derate linearly 5%/°C from 61 to 71°C)
-25 to +85°C
20 - 90% RH (non condensing)
Convection
Input to Output 3kVAC for 1 min.
Half sine wave, 4G, 22ms, 3 times per face, X, Y, Z
10-500Hz (20 min sweep) 0.002G2/Hz, 1Grms acceleration X, Y, Z, 1 hour
>100M at 25C & 70%RH, Output to Ground 500VDC
UL60950-1, UL508, UL1310(3) (Class 2), EN60950-1, CE Mark
EN55011, EN55022 Class B Radiated & Conducted, EN61000-6-3
EN61000-6-2, EN61000-4-2 Level4, EN61000-4-3, EN61000-4-6 Level 3
EN61000-4-4 Level 4 (I/P) Level 3 (O/P), EN61000-4-5 Level 4, EN61000-4-8, EN61000-4-11
130
260
390
23 x 75 x 97
45 x 75 x 91
73 x 75 x 97
Plastic
287,000
>288,000
273,000
239,000
2 years
(1) Auto Select - DPP100 only
(2) Recommend 25mm clearance on all sides.
(3) Does not include DPP25-5 & DPP100-24 models.
Evaluated to NEC NFPA70 Class 2 output per UL1310.