RSN-5-50B Datasheet, PDF (1/3 Pages) Riedon Powertron – DC Ammeter Shunts / Busbar Shunts 1 Amp - 500 Amp | |||
|
RSN Series
DC Ammeter Shunts / Busbar Shunts
1 Amp - 500 Amp
⢠1 Amp to 500 Amp
⢠0.1% Tolerance
⢠Manganin Resistive Element
⢠Calibration Certiï¬cate Available
⢠Common Application:
Power Supply
Power Converters
Current Measurements
Type
RSN-1
RSN-2
RSN-5
RSN-10
RSN-20
RSN-50
RSN-100
RSN-150
RSN-200
RSN-250
RSN-300
RSN-400
RSN-500
Rated
Current (A)
1
2
5
10
20
50
100
150
200
250
300
400
500
SPECIFICATIONS
Operating
Current (A)
0.667
1.33
3.33
6.67
13.33
33.33
66.67
100
133.33
166.67
200
266.67
333.33
Resistance (mâ¦)
50mV Output
50
25
10
5.0
2.5
1.0
0.5
0.333
0.25
0.20
0.167
0.125
0.10
Resistance (mâ¦)
100mV Output
100
50
20
10
5.0
2.0
1.0
0.667
0.50
0.40
0.333
0.25
0.20
SPECIFICATIONS
Rated Output
50mV, 100mV, Custom
Voltage Tolerance
±0.1%
Operating Temp.
Storage Temp.
Materials
30°C to 70°C
-55°C to 80°C
Resistance Element: Manganin
Terminal Block RSN: Brass
Base: Bakelite
Manganin Temperature Coe cient of Resistance ±15 PPM/C
+0.04
+0.02
0
-0.02
-0.04
-0.06
-0.08
-0.10
-0.12
10 20 30 40 50 60 70 80 90 100
Temperature °C
*Applies to resistance element only
Operating Current Derating: For continuous operation, it is recommended that shunts are not run at more than
two thirds (2/3) the rated current under normal conditions per IEEE standards for DC instrument shunts. At ambient
temperatures above 40°C, the current must be further derated to prevent damage.
Riedon Inc.
02/17
300 Cypress Avenue
Alhambra CA 91801
www.riedon.com
(626) 284-9901