English
Language : 

PCU10000 Datasheet, PDF (58/96 Pages) Red Lion Controls. Inc – THE PROCESS CONTROL UNIT
RECEIVING DATA
Data is transmitted from the PCU when a “T” Transmit Value or a “P”
Transmit Print Options command is sent to the unit via the serial port. Data is
also transmitted when the User Input, programmed for the Print Request
function, is activated. The print rate feature allows the selected print options
to be transmitted at a programmable rate over the serial port. The format for a
typical transmission string with mnemonics is shown in Figure 23, Typical
Transmission String:
Figure 23, Typical Transmission String
The first two digits transmitted are the unit address. If the unit address is 0,
the first two digits are blank. A space follows the unit address digits. The next
three characters are the mnemonics followed by one or more blank spaces.
The numerical data value is transmitted next followed by the identifying
units. Negative values are indicated by a “-” sign.
The decimal point position “floats” within the data field depending on
the actual value it represents. The numeric data is right justified without
leading zeros.
When a “T” command or print request is issued, the above character string
is sent for each line of a block transmission. An extra <SP><CR><LF> is
transmitted following the last line of transmission from a print request, to
provide separation between print-outs.
If abbreviated transmission is selected, only numeric data is sent. If
abbreviated transmission is not selected, the unit transmits mnemonics and
the numeric data.
If more than one string is transmitted there is a 100 msec minimum to 200
msec maximum built-in time delay after each transmission string and after
each block of transmission. When interfacing to a printer, sending
mnemonics are usually desirable.
Examples of transmissions are shown below:
1 INP 500U<CR><LF>100 - 200 msec
Mnemonics Sent
1 SET 525U<CR><LF>100 - 200 msec
1 PWR 20%<SP><CR><LF><SP><CR><LF>100 - 200 msec
-673.5<CR><LF>100 - 200 msec
No Mnemonics Sent
The Print Options provide a choice of which PCU data values are to be
transmitted. The PCU transmits the Print Options when either the User Input,
programmed for the print request function is activated, a “P” (Transmit Print
Options) command is sent to the PCU via the serial port, or the Automatic
Print Rate is set for a specific time. The Print Options are programmed in the
Serial Communications Module (6-SC) with the available options:
1. Print Input Display Value.
2. Print Setpoint Value.
3. Print % Output Power Value.
4. Print % Proportional Band Value.
5. Print Integral Time Value.
6. Print Derivative Time Value.
7. Print Alarm 1 Value.
8. Print Alarm 2 Value.
9. Print Deviation From Setpoint Value.
10. Print % Output Power Offset Value.
11. Print Setpoint Ramp Rate Value.
12. Print Relative Gain Value.
13. Print Deadband Value.
14. Print Output Status
15. Print Remote Setpoint Ratio
16. Print Remote Setpoint Bias
17. Print Proportional Band #2
18. Print Integral Time #2
19. Print Derivative Time #2
20. Print Second Input Reading
21. Print Remote Setpoint Reading
22. Print Secondary Setpoint Value
-50-